Schneider Electric PowerLogic ION6200 logging - MODBUS registers map


The following data can be automatically logger 24x7 to a database, CSV files or Excel with the help of the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software.

MODBUS offset
Description
Units
Data type
2
Firmware revision
 
word
3
Oem identification
 
word
4
Meter options
 
dword
6
# meter power ups
 
word
7
# peak demand resets
 
word
8
Meter on-time
 
dword
10
# flash erase cycles
 
dword
12
Device type
 
word
14
Demand interval down counter
 
word
99
Vln a
 
word
100
Vln b
 
word
101
Vln c
 
word
102
Vln avg
 
word
103
Vll ab
 
word
104
Vll bc
 
word
105
Vll ca
 
word
106
Vll avg
 
word
107
I a
 
word
108
I b
 
word
109
I c
 
word
110
I avg
 
word
111
I demand
 
word
112
I peak demand
 
word
113
I4
 
word
114
Frequency
 
smallint
115
PF sign total
 
smallint
116
PF sign a
 
smallint
117
PF sign b
 
smallint
118
PF sign c
 
smallint
119
kW total
 
smallint
120
kVAR total
 
smallint
121
kVA total
 
smallint
122
kW a
 
smallint
123
kW b
 
smallint
124
kW c
 
smallint
125
kVAR a
 
smallint
126
kVAR b
 
smallint
127
kVAR c
 
smallint
128
kVA a
 
smallint
129
kVA b
 
smallint
130
kVA c
 
smallint
131
kW demand
 
smallint
132
kW peak demand
 
smallint
133
kVAR demand
 
smallint
134
kVA demand
 
smallint
135
kVAR peak demand
 
smallint
136
kVA peak demand
 
smallint
137
kWh del
 
dword
139
kWh rec
 
dword
141
kVARh del
 
dword
There are more MODBUS items for this device. Please download the program to discover all registers.