Eastron (X96) logging - MODBUS registers map
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Eastron (X96) logging and record.
MODBUS offset
Description
Units
Data type
2
Phase 2 line to neutral volts
V
single
4
Phase 3 line to neutral volts
V
single
12
Phase 1 active power
W
single
14
Phase 2 active power
W
single
16
Phase 3 active power
W
single
18
Phase 1 apparent power
VA
single
20
Phase 2 apparent power
VA
single
22
Phase 3 apparent power
VA
single
24
Phase 1 reactive power
VAr
single
26
Phase 2 reactive power
VAr
single
28
Phase 3 reactive power
VAr
single
30
Phase 1 power factor (1)
None
single
32
Phase 2 power factor (1)
None
single
34
Phase 3 power factor (1)
None
single
36
Phase 1 phase angle
Degrees
single
38
Phase 2 phase angle
Degrees
single
40
Phase 3 phase angle
Degrees
single
42
Average line to neutral volts
V
single
46
Average line current
A
single
48
Sum of line currents
A
single
52
Total systerrt power
W
single
56
Total systerrt volt arrtps
VA
single
60
Total system var
VAr
single
62
Total systerrt power factor (1)
None
single
66
Total systerrt phase angle
Degrees
single
70
Frequency of supply voltages
Hz
single
72
Import wh since last reset
kWh
single
74
Export wh since last reset
kWH
single
76
Import varh since last reset
kVArh
single
78
Export varh since last reset
kVArh
single
80
Vah since last reset
kVAh
single
82
Ah since last reset
Ah
single
84
Total systerrt power derrtand (2)
W
single
86
Maxirrturrt total systerrt power derrtand (2)
W
single
88
Import active power derrtand
W
single
90
Import active power rrtax. Derrtand
W
single
92
Export active power derrtand
W
single
94
Export active power rrtax. Derrtand
W
single
100
Total system va demand
VA
single
102
Maximum total system va demand
VA
single
104
Neutral current demand
Ops
single
106
Maximum neutral current demand
AlIipS
single
108
Total systerrt reactive power derrtand. (2)
VAr
single
110
Maxirrturrt total systerrt reactive power demand (2)
VAr
single
160
Voltage phase sequence (normal=1 reverse=2
None
single
162
Current phase sequence (normal=1 reverse=2
None
single
192
Nature of the load ( resistive =1 inductive =2 capacitive =3
None
single
There are more MODBUS items for this device. Please download the program to discover all registers.