bg

Eaton (IQ100 series,IQ130,IQ140,IQ150) data logger - MODBUS registers map


The following data can be automatically logger 24x7 to a database, CSV files or Excel with the help of the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software.

MODBUS offset
Description
Units
Data type
16
Meter type
bit-mapped
word
17
Firmware version
 
string(4)
19
Map version
0 to 65535
word
20
Meter configuration
bit-mapped
word
21
Asic version
0-65535
word
899
Watts, 3 ph total
Watt
single
901
Vars, 3 ph total
VARs
single
903
Vas, 3 ph total
VAs
single
999
Voits A N
voIts
single
1001
Voits B N
volts
single
1003
Voits C N
voIts
single
1005
Voits A B
volts
single
1007
Voits B C
volts
single
1009
Voits C A
volts
single
1011
Amps A
amps
single
1013
Amps B
amps
single
1015
Amps C
amps
single
1017
Watts, 3 ph total
watts
single
1019
Vars, 3 ph total
VARs
single
1021
Vas, 3 ph total
VAs
single
1025
Frequency
Hz
single
1027
Neutral current
amps
single
1099
W hours, received
Wh
integer
1101
W hours, delivered
Wh
integer
1103
W hours, net
Wh
integer
1105
W hours, total
Wh
integer
1107
Var hours, positive
VARh
integer
1109
Var hours, negative
VARh
integer
1111
Var hours, net
VARh
integer
1113
Var hours, total
VARh
integer
1115
Va hours, total
0 to 99999999
integer
1999
Amps a, average
amps
single
2001
Amps b, average
amps
single
2003
Amps c, average
amps
single
2005
Positive watts, 3 ph, average
watts
single
2007
Positive vars, 3 ph, average
VARs
single
2009
Negative watts, 3 ph, average
watts
single
2011
Negative vars, 3 ph, average
VARs
single
2013
Vas, 3 ph, average
-9999 M to +9999 M
single
2015
Positive pf, 3 ph, average
-1.00 to +1.00
single
2017
Negative pf, 3 pf, average
-1.00 to +1.00
single
3001
Volts B n, minimum
Volt
single
3129
Negative power factor, 3 ph, maximum avg demand
-1.00 to +1.00
single
4099
Phase A current
-1800 to +1800
smallint
4100
Phase B current
-1800 to +1800
smallint
4101
Phase C current
-1800 to +1800
smallint
4102
Angle, volts A B
-1800 to +1800
smallint
4103
Angle, volts B C
-1800 to +1800
smallint
4104
Angle, volts C A
-1800 to +1800
smallint
4999
Meter status
bit-mapped
word
There are more MODBUS items for this device. Please download the program to discover all registers.

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.