bg

Siemens Sentron PAC MODBUS logger. Registers Map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Siemens Sentron PAC logger and capture.

Siemens Sentron PAC 3200 - MODBUS Registers

MODBUS offset
Description
Units
Data type
1
Voltage Va-n
V
single
3
Voltage Vb-n
V
single
5
Voltage Vc-n
V
single
7
Voltage Va-b
V
single
9
Voltage Vb-c
V
single
11
Voltage Vc-a
V
single
13
Current a
A
single
15
Current b
A
single
17
Current c
A
single
19
Apparent Power a
V
single
21
Apparent Power b
V
single
23
Apparent Power c
V
single
25
Active Power a
W
single
27
Active Power b
W
single
29
Active Power c
W
single
31
Reactive Power a
v
single
33
Reactive Power b
v
single
35
Reactive Power c
v
single
37
Power Factor a
-
single
39
Power Factor b
-
single
41
Power Factor c
-
single
43
THD-R Voltage a
%
single
45
THD-R Voltage b
%
single
47
THD-R Voltage c
%
single
49
THD-R Current a
%
single
51
THD-R Current b
%
single
53
THD-R Current c
%
single
55
Frequency
H
single
57
Average Voltage Vph-n
V
single
59
Average Voltage Vph-ph
V
single
61
Average Current
A
single
63
Total Apparent Power
V
single
65
Total Active Power
W
single
67
Total Reactive Power
v
single
69
Total Power Factor
-
single
71
Amplitude Unbalance - Voltage
%
single
73
Amplitude Unbalance - Current
%
single
75
Maximum Voltage Va-n
V
single
77
Maximum Voltage Vb-n
V
single
79
Maximum Voltage Vc-n
V
single
81
Max. Voltage Va-b
V
single
83
Max. Voltage Vb-c
V
single
85
Max. Voltage Vc-a
V
single
87
Maximum Current a
A
single
89
Maximum Current b
A
single
91
Maximum Current c
A
single
93
Maximum Apparent Power a
V
single
95
Maximum Apparent Power b
V
single
97
Maximum Apparent Power c
V
single
99
Maximum Active Power a
W
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Siemens Sentron PAC 4200 - Mapping

MODBUS offset
Description
Units
Data type
1
Voltage a-n
V
single
3
Voltage b-n
V
single
5
Voltage c-n
V
single
7
Voltage a-b
V
single
9
Voltage b-c
V
single
11
Voltage c-a
V
single
13
Current a
A
single
15
Current b
A
single
17
Current c
A
single
19
Apparent Power a
V
single
21
Apparent Power b
V
single
23
Apparent Power c
V
single
25
Active Power a
W
single
27
Active Power b
W
single
29
Active Power c
W
single
31
Reactive Power a (VARn)
V
single
33
Reactive Power b (VARn)
V
single
35
Reactive Power c (VARn)
V
single
37
Power Factor a
-
single
39
Power Factor b
-
single
41
Power Factor c
-
single
43
THD Voltage a-b
%
single
45
THD Voltage b-c
%
single
47
THD Voltage c-a
%
single
55
Line Frequency
H
single
57
3-Phase Average Voltage ph-n
V
single
59
3-Phase Average Voltage ph-ph
V
single
61
3-Phase Average Current ph-ph
A
single
63
Total Apparent Power
V
single
65
Total Active Power
W
single
67
Total Reactive Power (VARn)
V
single
69
Total Power Factor
-
single
71
Amplitude Unbalance Voltage
%
single
73
Amplitude Unbalance Current
%
single
75
Maximum Voltage a-n
V
single
77
Maximum Voltage b-n
V
single
79
Maximum Voltage c-n
V
single
81
Maximum Voltage a-b
V
single
83
Maximum Voltage b-c
V
single
85
Maximum Voltage c-a
V
single
87
Maximum Current a
A
single
89
Maximum Current b
A
single
91
Maximum Current c
A
single
93
Maximum Apparent Power a
V
single
95
Maximum Apparent Power b
V
single
97
Maximum Apparent Power c
V
single
99
Maximum Active Power a
W
single
101
Maximum Active Power b
W
single
103
Maximum Active Power c
W
single
105
Maximum Reactive Power a (VARn)
V
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Siemens Sentron PAC 2200 - MODBUS Registers

MODBUS offset
Description
Units
Data type
1
Voltage VL1 N
V
single
3
Voltage vlz
V
single
5
Voltage vl N
V
single
7
Voltage VL1 L2
V
single
9
Voltage vlz L3
V
single
11
Voltage vl L1
V
single
13
Current L1
A
single
15
Current L2
A
single
17
Current L3
A
single
19
Apparent power L1
VA
single
21
Apparent power L2
VA
single
23
Apparent power L3
VA
single
25
Active power L1
W
single
27
Active power L2
W
single
29
Active power L3
W
single
31
Reactive power L1
var
single
33
Reactive power L2
var
single
35
Reactive power L3
var
single
37
Power factor L1
 
single
39
Power factor L2
 
single
41
Power factor L3
 
single
55
Frequency
Hz
single
57
Average voltage V L-N
V
single
59
Average voltage V L-L
V
single
61
Average current
A
single
63
Total apparent power
VA
single
65
Total active power
W
single
67
Total reactive power
var
single
69
Total power factor
 
single
205
Device diagnostics and device status
 
dword
207
Status of the digital outputs
 
dword
209
Status of the digital inputs
 
dword
211
Active tariff
 
dword
215
Universal counter
 
dword
217
Relevant parameter changes counter
 
dword
219
Counter all parameter changes
 
dword
501
Cumulated active power import
W
single
503
Cumulated reactive power import
var
single
505
Cumulated active power export
W
single
507
Cumulated reactive power export
var
single
509
Maximum active power reading during the period
W
single
511
Minimum active power reading during the period
W
single
513
Maximum reactive power reading dur ing the period
var
single
515
Minimum reactive power reading dur ing the period
var
single
517
Length of the current measuring period
s
dword
519
Time since start of the active demand period
s
dword
801
Active energy import tariff 1
Wh
double
805
Active energy import tariff 2
Wh
double
809
Active energy export tariff 1
Wh
double
813
Active energy export tariff 2
Wh
double
There are more MODBUS items for this device. Please download the program to discover all registers.