bg

Seneca MODBUS data logging. Registers Map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Seneca data logging and read.

Seneca (S203) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
134
Voltage A
 
single
136
Voltage B
 
single
138
Voltage C
 
single
140
Voltage 3ph
 
single
192
Voltage A
 
word
193
Voltage B
 
word
194
Voltage C
 
word
195
Voltage 3ph
 
word
142
Current A
 
single
144
Current B
 
single
146
Current C
 
single
148
Current 3ph
 
single
196
Current A
 
word
197
Current B
 
word
198
Current C
 
word
199
Current 3ph
 
word
150
Active pow A
 
single
152
Active pow B
 
single
154
Active pow C
 
single
156
Active pow 3ph
 
single
200
Active pow A
 
word
201
Active pow B
 
word
202
Active pow C
 
word
203
Active pow 3ph
 
word
158
Reactive pow A
 
single
160
Reactive pow B
 
single
162
Reactive pow C
 
single
164
Reactive pow 3 ph
 
single
204
Reactive pow A
 
word
205
Reactive pow B
 
word
206
Reactive pow C
 
word
207
Reactive pow 3 ph
 
word
166
Apparent pow A
 
single
168
Apparent pow B
 
single
170
Apparent pow C
 
single
172
Apparent pow 3 ph
 
single
208
Apparent pow A
 
word
209
Apparent pow B
 
word
210
Apparent pow C
 
word
211
Apparent pow 3 ph
 
word
184
Energy A
 
single
186
Energy B
 
single
188
Energy C
 
single
190
Energy 3ph
 
single
174
Cos A
 
single
176
Cos B
 
single
178
Cos C
 
single
180
Cos 3ph
 
single
212
Cos A
 
word
213
Cos B
 
word
There are more MODBUS items for this device. Please download the program to discover all registers.

Seneca (S604) - MODBUS Registers

MODBUS offset
Description
Units
Data type
4096
Phase 1 N voltage
V
single
4098
Phase 2 N voltage
V
single
4100
Phase 3 N voltage
V
single
4102
Line 12 voltage
V
single
4104
Line 23 voltage
V
single
4106
Line 31 voltage
V
single
4108
System voltage
V
single
4110
Phase 1 current
A
single
4112
Phase 2 current
A
single
4114
Phase 3 current
A
single
4116
Neutral current
A
single
4118
System current
A
single
4120
Phase 1 active power
W
single
4122
Phase 2 active power
W
single
4124
Phase 3 active power
W
single
4126
System active power
W
single
4128
Phase 1 apparent power
VA
single
4130
Phase 2 apparent power
VA
single
4132
Phase 3 apparent power
VA
single
4134
System apparent power
VA
single
4136
Phase 1 reactive power
var
single
4138
Phase 2 reactive power
var
single
4140
Phase 3 reactive power
var
single
4142
System reactive power
var
single
4144
Phase 1 power factor
 
single
4146
Phase 2 power factor
 
single
4148
Phase 3 power factor
 
single
4150
System power factor
 
single
4152
Phase 1 dpf
 
single
4154
Phase 2 dpf
 
single
4156
Phase 3 dpf
 
single
4158
Phase 1 tangent
 
single
4160
Phase 2 tangent
 
single
4162
Phase 3 tangent
 
single
4164
System tangent
 
single
4166
Phase 1 N voltage thd
%
single
4168
Phase 2 N voltage thd
%
single
4170
Phase 3 N voltage thd
%
single
4172
Line 12 voltage thd
%
single
4174
Line 23 voltage thd
%
single
4176
Line 31 voltage thd
%
single
4178
Phase 1 current thd
%
single
4180
Phase 2 current thd
%
single
4182
Phase 3 current thd
%
single
4184
Neutral current thd
%
single
4186
Frequency
Hz
single
4188
Sequence ($00=123 ccw, $01=321 cw, $02=not defined)
 
single
4190
Hourcounter
h
single
4192
Hourcounter
h
single
4366
Phase 1 current dmd
A
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Seneca (S700) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
4096
Phase 1 N voltage
V
single
4098
Phase 2 N voltage
V
single
4100
Phase 3 N voltage
V
single
4102
Line 12 voltage
V
single
4104
Line 23 voltage
V
single
4106
Line 31 voltage
V
single
4108
System voltage
V
single
4110
Phase 1 current
A
single
4112
Phase 2 current
A
single
4114
Phase 3 current
A
single
4116
Neutral current
A
single
4118
System current
A
single
4120
Phase 1 active power
W
single
4122
Phase 2 active power
W
single
4124
Phase 3 active power
W
single
4126
System active power
W
single
4128
Phase 1 apparent power
VA
single
4130
Phase 2 apparent power
VA
single
4132
Phase 3 apparent power
VA
single
4134
System apparent power
VA
single
4136
Phase 1 reactive power
var
single
4138
Phase 2 reactive power
var
single
4140
Phase 3 reactive power
var
single
4142
System reactive power
var
single
4144
Phase 1 power factor
 
single
4146
Phase 2 power factor
 
single
4148
Phase 3 power factor
 
single
4150
System power factor
 
single
4152
Phase 1 dpf
 
single
4154
Phase 2 dpf
 
single
4156
Phase 3 dpf
 
single
4158
Phase 1 tangent
 
single
4160
Phase 2 tangent
 
single
4162
Phase 3 tangent
 
single
4164
System tangent
 
single
4166
Phase 1 N voltage thd
%
single
4168
Phase 2 N voltage thd
%
single
4170
Phase 3 N voltage thd
%
single
4172
Line 12 voltage thd
%
single
4174
Line 23 voltage thd
%
single
4176
Line 31 voltage thd
%
single
4178
Phase 1 current thd
%
single
4180
Phase 2 current thd
%
single
4182
Phase 3 current thd
%
single
4184
Neutral current thd
%
single
4186
Frequency
Hz
single
4188
Sequence ($00=123 ccw, $01=321 cw, $02=not defined)
 
single
4190
Hourcounter
h
single
4192
Hourcounter
h
single
4366
Phase 1 current dmd
A
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Seneca (Z203) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
80
Voltage
 
single
94
Voltage
 
word
82
Current
 
single
95
Current
 
word
84
Active power
 
single
88
Reactive power
 
single
97
Reactive power
 
single
90
Cos
 
single
98
Cos
 
single
86
Freq
 
single
100
Frequency
 
word

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.