bg

Socomec (DIRIS U20) data logging - MODBUS registers map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Socomec (DIRIS U20) data logging and read.

MODBUS offset
Description
Units
Data type
36864
Inst. Measurement. Network. Date of last instance
s
dword
36866
Inst. Measurement. Network. Integration time
s
word
36867
Inst. Measurement. Network. Frequency
Hz
dword
36869
Inst. Measurement. Network. Ph N voltage : V1
V
dword
36871
Inst. Measurement. Network. Ph N voltage : V2
V
dword
36873
Inst. Measurement. Network. Ph N voltage : V3
V
dword
36875
Inst. Measurement. Network. Ph ph voltage : U12
V
dword
36877
Inst. Measurement. Network. Ph ph voltage : U23
V
dword
36879
Inst. Measurement. Network. Ph ph voltage : U31
V
dword
37120
Inst. Fundamental measurement. Network. Date of last instance
s
dword
37122
Inst. Fundamental measurement. Network. Integration time
s
word
37123
Inst. Fundamental measurement. Network. Ph N voltage: v1h1
V
dword
37125
Inst. Fundamental measurement. Network. Ph N voltage: v2h1
V
dword
37127
Inst. Fundamental measurement. Network. Ph N voltage: v3h1
V
dword
37129
Inst. Fundamental measurement. Network. Ph N voltage: vnh1
V
dword
37131
Inst. Fundamental measurement. Network. Ph N voltage phase: phv1h1
?
smallint
37132
Inst. Fundamental measurement. Network. Ph N voltage phase: phv2h1
?
smallint
37133
Inst. Fundamental measurement. Network. Ph N voltage phase: phv3h1
?
smallint
37134
Inst. Fundamental measurement. Network. Ph N voltage phase: phvnh1
?
smallint
37135
Inst. Fundamental measurement. Network. Ph ph voltage: u12h1
V
dword
37137
Inst. Fundamental measurement. Network. Ph ph voltage: u23h1
V
dword
37139
Inst. Fundamental measurement. Network. Ph ph voltage: u31h1
V
dword
37141
Inst. Fundamental measurement. Network. Ph ph voltage phase: phu12h1
?
smallint
37142
Inst. Fundamental measurement. Network. Ph ph voltage phase: phu23h1
?
smallint
37143
Inst. Fundamental measurement. Network. Ph ph voltage phase: phu31h1
?
smallint
37144
Inst. Fundamental measurement. Network. Ph N voltage total harmonic distortion : thd V1
%
word
37145
Inst. Fundamental measurement. Network. Ph N voltage total harmonic distortion : thd V2
%
word
37146
Inst. Fundamental measurement. Network. Ph N voltage total harmonic distortion : thd V3
%
word
37147
Inst. Fundamental measurement. Network. Ph ph voltage total harmonic distortion : thd U12
%
word
37148
Inst. Fundamental measurement. Network. Ph ph voltage total harmonic distortion : thd U23
%
word
37149
Inst. Fundamental measurement. Network. Ph ph voltage total harmonic distortion : thd U31
%
word

Related MODBUS registers maps