MODBUS offset
Description
Units
Data type
10511
Hour: operating hours counter
h
dword
10513
U12: conductor voltage
V
dword
10515
U23: conductor voltage
V
dword
10517
U31: conductor voltage
V
dword
10519
V1: conductor voltage to N
V
dword
10521
V2: conductor voltage to N
V
dword
10523
V3: conductor voltage to N
V
dword
10525
F: frequency
Hz
dword
10527
I1: current
A
dword
10529
I2: current
A
dword
10531
I3: current
A
dword
10533
In: neutral conductor current
A
dword
10535
P: total active power +/-
W
integer
10537
Q: total reactive power +/-
var
integer
10539
S: total apparent power
VA
dword
10541
PF: total power factor -: capacitive and +: inductive
1
integer
10543
P1: active power phase 1 +/-
W
integer
10545
P2: active power phase 2 +/-
W
integer
10547
P3: active power phase 3 +/-
W
integer
10549
Q1: reactive power phase 1 +/-
var
integer
10551
Q2: reactive power phase 2 +/-
var
integer
10553
Q3: reactive power phase 3 +/-
var
integer
10555
S1: apparent power phase 1
VA
dword
10557
S2: apparent power phase 2
VA
dword
10559
S3: apparent power phase 3
VA
dword
10561
PF1; power factor, phase 1 -: capacitive and +: inductive
1
integer
10563
PF2; power factor, phase 2 -: capacitive and +: inductive
1
integer
10565
PF3; power factor, phase 3 -: capacitive and +: inductive
1
integer
10567
ISYS: mean current value
A
dword
10569
USYS: mean value of line voltages
V
dword
10571
VSYS: mean value of line voltages to N
V
dword
10767
Hour: operating hours counter
h
dword
10769
Total active energy procurement system
kWh
dword
10771
Total inductive reactive energy system
kvarh
dword
10773
Total apparent energy system
kVAh
dword
10775
Total active energy supply system
kWh
dword
10777
Total capacitive reactive energy system
kvarh
dword
10779
Partial energy meter active energy pro- curement system
kWh
dword
10781
Partial energy meter inductive reactive energy system
kvarh
dword
10783
Partial energy meter apparent energy system
kVAh
dword
10785
Partial energy meter active energy sup- ply system
kWh
dword
10787
Partial energy meter capacitive reactive energy system
kvarh
dword

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.