bg

Meatrol (ME237) logging - MODBUS registers map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Meatrol (ME237) logging and record.

MODBUS offset
Description
Units
Data type
1000
Voltage value of phase A
V
single
1002
Voltage value of phase B
V
single
1004
Voltage value of phase C
V
single
1006
Average phase voltage value
V
single
1008
Voltage value of line A-B
V
single
1010
Voltage value of line B-C
V
single
1012
Voltage value of line C-A
V
single
1014
Average line voltage value
V
single
1016
Current value of phase A
A
single
1018
Current value of phase B
A
single
1020
Current value of phase C
A
single
1022
Average value of three-phase current
A
single
1026
Active power of phase A
W
single
1028
Active power of phase B
W
single
1030
Active power of phase C
W
single
1032
Sum of three-phase active power
W
single
1034
Reactive power of phase A
Var
single
1036
Reactive power of phase B
Var
single
1038
Reactive power of phase C
Var
single
1040
Sum of three-phase reactive power
Var
single
1042
Apparent power of phase A
Va
single
1044
Apparent power of phase B
Va
single
1046
Apparent power of phase A
Va
single
1048
Sum of three-phase apparent power
Va
single
1050
Power factor of phase A
 
single
1052
Power factor of phase B
 
single
1054
Power factor of phase C
 
single
1056
Average power factor
 
single
1058
Fundamental power factor of phase A
 
single
1060
Fundamental power factor of phase B
 
single
1062
Fundamental power factor of phase C
 
single
1064
Average fundamental power factor
 
single
1066
Grid frequency
Hz
single
2000
Percentage of total harmonic of voltage of phase A
%
single
2002
Percentage of total harmonic of voltage of phase B
%
single
2004
Percentage of total harmonic of voltage of phase A
%
single
2006
Three phase voltage total harmonic percentage average
%
single
2008
Percentage of total harmonic current of phase A
%
single
2010
Percentage of total harmonic current of phase B
%
single
2012
Percentage of total harmonic current of phase C
%
single
2014
Percentage average value of total harmonic of three-phase current
%
single
4000
Positive active energy of phase A
0.1kWh
dword
4002
Positive active energy of phase B
0.1kWh
dword
4004
Positive active energy of phase C
0.1kWh
dword
4006
Sum of three-phase positive active energy
0.1kWh
dword
4008
Reverse active electric energy of phase A
0.1kWh
dword
4010
Reverse active electric energy of phase B
0.1kWh
dword
4012
Reverse active electric energy of phase C
0.1kWh
dword
4014
Sum of three-phase reverse active energy
0.1kWh
dword
4024
Positive reactive energy of phase A
0.1kVarh
dword
There are more MODBUS items for this device. Please download the program to discover all registers.