Lovato (DME) logging - MODBUS registers map
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Lovato (DME) logging and log.
MODBUS offset
Description
Units
Data type
20
L1 active power
W
integer
22
L2 active power
W
integer
24
L3 active power
W
integer
26
L1 reactive power
Var
integer
28
L2 reactive power
Var
integer
30
L3 reactive power
Var
integer
32
L1 apparent power
VA
dword
34
L2 apparent power
VA
dword
36
L3 apparent power
VA
dword
38
L1 power factor
integer
40
L2 power factor
integer
42
L3 power factor
integer
52
Eqv. Phase voltage
V
dword
54
Eqv. Phase to phase voltage
V
dword
58
Eqv. Active power
W
integer
60
Eqv. Reactive power
var
integer
62
Eqv. Apparent power
VA
dword
64
Eqv power factor
integer
66
Phase phase voltage asymmetry
%
dword
68
Phase neural voltage asymmetry
%
dword
70
Current asymmetry
%
dword
1024
L1 phase voltage
V
dword
1026
L2 phase voltage
V
dword
1094
Neutral current
%
dword
1536
L1 phase voltage
V
dword
1538
L2 phase voltage
V
dword
1606
Neutral current
%
dword
2118
Neutral current
%
dword
2562
L2 phase voltage
V
dword
2630
Neutral current
%
dword
6944
Total imp. Active energy
kWh
dword
6948
Total exported active energy
kWh
dword
6952
Total imp. Reactive energy
kvarh
dword
6956
Total exp. Reactive energy
kvarh
dword
6960
Total apparent energy
KVAh
dword
There are more MODBUS items for this device. Please download the program to discover all registers.