MODBUS offset
Description
Units
Data type
40005
Manufacturer
string(32)
40021
Device model
string(32)
40045
Sw version of inverter
string(16)
40053
Serialnumber of the inverter
string(32)
40069
Modbus device address
word
40072
Ac total current value
single
40074
Ac phase A current value
single
40076
Ac phase B current value
single
40078
Ac phase C current value
single
40080
Ac voltage phase ab value
single
40082
Ac voltage phase bc value
single
40084
Ac voltage phase ca value
single
40086
Ac voltage phase A to neutral value
single
40088
Ac voltage phase B to neutral value
single
40090
Ac voltage phase C to neutral value
single
40092
Ac power value
single
40094
Ac frequency value
Hz
single
40096
Apparent power
VA
single
40098
Reactive power
VAr
single
40102
Ac lifetime energy production
Wh
single
40108
Dc power value
single
40120
Event flags (bits 0 31)
dword
40122
Event flags (bits 32 63)
dword
40124
Vendor defined event flags (bits 0 31)
dword
40126
Vendor defined event flags (bits 32 63)
dword
40128
Vendor defined event flags (bits 64 95)
dword
40130
Vendor defined event flags (bits 96 127)
dword
40133
Length of nameplate model
word
40135
Continuous power output capability of the inverter
word
40137
Continuous volt ampere capability of the inverter
VA
word
40139
Continuous var capability of the inverter in quadrant 1
var
smallint
40142
Continuous var capability of the inverter in quadrant 4
var
smallint
40144
Maximum rms ac current level capability of the inverter
word
40146
Minimum power factor capability of the inverter in quadrant 1
smallint
40149
Minimum power factor capability of the inverter in quadrant 4
smallint
40151
Nominal energy rating of storage device
Wh
word
40155
Maximum rate of energy transfer into the storage device
word
40157
Maximum rate of energy transfer out of the storage device
word
40161
Length of basic settings model
word
40162
Setting for maximum power output. Default to i_wrtg
word
40163
Voltage at the pcc
word
40164
Offset from pcc to inverter
smallint
40167
Setpoint for maximum apparent power. Default to i_vartg
VA
word
40168
Setting for maximum reactive power in quadrant 1. Default to varrtgq1
var
smallint
40171
Setting for maximum reactive power in quadrant 4 default to varrtgq4
var
smallint
40173
Setpoint for minimum power factor value in quadrant 1. Default to pfrtgq1
smallint
40176
Setpoint for minimum power factor value in quadrant 4. Default to pfrtgq4
smallint
40193
Length of measurements_status model
word
There are more MODBUS items for this device. Please download the program to discover all registers.