MODBUS offset
Description
Units
Data type
1280
V1
V
dword
1282
V2
V
dword
1284
V3
V
dword
1288
U12
V
dword
1290
U23
V
dword
1292
U31
V
dword
1294
I1
A
dword
1296
I2
A
dword
1298
I3
A
dword
1300
In
A
dword
1302
P1
W
integer
1304
P2
W
integer
1306
P3
W
integer
1308
Pt
W
integer
1310
Q1
var
integer
1312
Q2
var
integer
1314
Q3
var
integer
1316
Qt
var
integer
1318
S1
VA
dword
1320
S2
VA
dword
1322
S3
VA
dword
1324
St
VA
dword
1326
FP1
 
smallint
1327
Quadrant FP1
 
word
1328
FP2
 
smallint
1329
Quadrant FP2
 
word
1330
FP3
 
smallint
1331
Quadrant FP3
 
word
1332
Fpt
 
smallint
1333
Quadrant, fpt
 
word
1348
Frequency
Hz
word
1350
Total tan phi
 
integer
2832
Minima of pt receiver
W
dword
2836
Minima of pt generator
W
dword
3140
Minima of st
VA
dword
2868
Maxima of V1
V
dword
2872
Maxima of V2
V
dword
2876
Maxima of V3
V
dword
2880
Maxima of vt
V
dword
2884
Maxima of U12
V
dword
2888
Maxima of U23
V
dword
2892
Maxima of U31
V
dword
2896
Maxima dofi1
A
dword
2900
Maxima of I2
A
dword
2904
Maxima of I3
A
dword
2908
Maxima of in
A
dword
2936
Maxima of pt receiver
W
dword
2940
Maxima of pt generator
W
dword
2968
Maxima of qt receiver
var
integer
2972
Maxima of qt generator
var
integer
There are more MODBUS items for this device. Please download the program to discover all registers.