bg

Veris MODBUS data logging. Registers Map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Veris data logging and capture.

Veris (E23) - MODBUS Registers

MODBUS offset
Description
Units
Data type
1537
Real energy (ph) consumption
kWh
single
1539
Reactive energy (qh) consumption
kVARh
single
1541
Apparent energy (sh) consumption
kVAh
single
1543
Total instantaneous real power (p)
kW
single
1545
Total instantaneous reactive power (q)
kVAR
single
1547
Total instantaneous apparent power (s)
kVA
single
1549
Average power factor (pf: total kw / total kva)
Ratio
single
1551
Voltage line to line (u), average of active phases
Volt
single
1553
Voltageline to neutral (v), average of active phases
Volt
single
1555
Current, average of active phases
Amp
single
1557
Frequency (derived from phase a, b, or C in that order)
Hz
single
1559
Total real power present demand
kW
single
1561
Total reactive power present demand
kVAR
single
1563
Total apparent power present demand
kVA
single
1565
Total real power max demand
kW
single
1567
Total reactive power max demand
kVAR
single
1569
Total apparent power max demand
kVA
single
1577
Pulse counter 1 (real energy)
 
single
1579
Pulse counter 2 (reactive energy)
 
single
1589
Real energy consumption, L1
kWh
single
1591
Real energy consumption, L2
kWh
single
1593
Real energy consumption, L3
kWh
single
1595
Reactive energy consumption, L1
kWh
single
1597
Reactive energy consumption, L2
kWh
single
1599
Reactive energy consumption, L3
kWh
single
1601
Apparent energy consumption, L1
kWh
single
1603
Apparent energy consumption, L2
kWh
single
1605
Apparent energy consumption, L3
kWh
single
1607
Real power, L1
kW
single
1609
Real power, L2
kW
single
1611
Real power, L3
kW
single
1613
Reactive power, L1
kVAR
single
1615
Reactive power, L2
kVAR
single
1617
Reactive power, L3
kVAR
single
1619
Apparent power, L1
kVA
single
1621
Apparent power, L2
kVA
single
1623
Apparent power, L3
kVA
single
1625
Power factor, L1
Ratio
single
1627
Power factor, L2
Ratio
single
1629
Power factor, L3
Ratio
single
1631
Voltage, L1 L2
Volt
single
1633
Voltage, L2 L3
Volt
single
1635
Voltage, L3 L1
Volt
single
1637
Voltage, L1 N
Volt
single
1639
Voltage, L2 N
Volt
single
1641
Voltage, L3 N
Volt
single
1643
Current, phase A
Amp
single
1645
Current, phase B
Amp
single
1647
Current, phase C
Amp
single
1649
Current, neutral
Amp
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Veris (E34) - MODBUS Registers

MODBUS offset
Description
Units
Data type
10101
Total kwh (msw)
kWh
single
10109
Total kw
kW
single
10113
Total kva
kVA
single
10115
Total pf
PF
single
10119
Average current
Amperes
single
10121
Present kw demand
kW
single
10127
Present current demand
Amperes
single
10129
Max kw demand
kW
single
10135
Max current demand
Amperes
single
10137
Max kw
kW
single
10143
Max current
Amperes
single
10145
Voltage, L l, average of 3 phases
Volts
single
10147
Voltage, L n, average of 3 phases
Volts
single
10149
Frequency (derived from phase a)
Hertz
single
10151
Thd current, weighted average of 3 phases
 
single
10153
Thd voltage L l, weighted average of 3 phases
 
single
10155
Thd voltage L n, weighted average of 3 phases
 
single
10157
Snapshot kwh (msw)
kWh
single
10301
Kwh (msw)
kWh
single
10309
Kw
kW
single
10313
Kva
kVA
single
10315
Pf
PF
single
10317
Current angle
degrees-angular
single
10319
Current
Amperes
single
10321
Present kw demand
kW
single
10327
Present current demand
Amperes
single
10329
Max kw demand
kW
single
10335
Max current demand
Amperes
single
10337
Max kw
kW
single
10343
Max current
Amperes
single
10345
Voltage, L L
Volts
single
10347
Voltage, L N
Volts
single
10349
Frequency (derived from phase a)
Hertz
single
10351
Thd current
 
single
10353
Thd voltage L L
 
single
10355
Thd voltage L N
 
single
10357
Kwh snapshot (msw)
kWh
single
10501
Kwh (msw)
kWh
single
10509
Kw
kW
single
10513
Kva
kVA
single
10515
Pf
PF
single
10517
Current angle
degrees-angular
single
10519
Current
Amperes
single
10521
Present kw demand
kW
single
10527
Present current demand
Amperes
single
10529
Max kw demand
kW
single
10535
Max current demand
Amperes
single
10537
Max kw
kW
single
10543
Max current
Amperes
single
10545
Voltage, L L
Volts
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Veris (E50) - Mapping

MODBUS offset
Description
Units
Data type
1
Real energy consumption
kWh
dword
3
Total instantaneous real power (3 phase total)
kW
word
4
Total instantaneous reactive power (3 phase total)
kVAR
word
5
Total instantaneous apparent power (3 phase total)
KVA
word
6
Total power factor (total kw /total kva)
Ratio
word
7
Voltage, L l, average of 3 phases
Volt
word
8
Voltage, L ii, average of 3 phases
Volt
word
9
Current, average of 3 phases
Amp
word
10
Real power, phase A
kW
word
11
Real power, phase B
kW
word
12
Real power, phase C
kW
word
13
Power factor, phase A
Ratio
word
14
Power factor, phase B
Ratio
word
15
Power factor, phase C
Ratio
word
16
Voltage, phase A B
Volt
word
17
Voltage, phase B C
Volt
word
18
Voltage, phase A C
Volt
word
19
Voltage, phase A N
Volt
word
20
Voltage, phase B N
Volt
word
21
Voltage, phase C N
Volt
word
22
Current, instantaneous, phase A
Amp
word
23
Current, instantaneous, phase B
Amp
word
24
Ljrrent, instantaneous, phase C
Amp
word
26
Frequency (derived from phase A)
Hz
word
31
Apparent power phase A
KVA
word
32
Apparent power phase B
KVA
word
34
Reactive power, phase A
kVAR
word
35
Reactive power, phase B
kVAR
word
36
Reactive power, phase C
kVAR
word
37
Total real power present demand
kW
word
38
Total reactive power present demand
kVAR
word
39
Total apparent power present demand
KVA
word
40
Total real power max demand
kW
word
41
Total reactive power max demand
kVAR
word
42
Total apparent power max demand
KVA
word
257
Real energy consumption (clear via reset register)
kWh
single
259
Real energy consumption (clear via reset register)
kWh
single
261
Total instantaneous real power
kW
single
263
Total instantaneous reactive power
kVAk
single
265
Total instantaneous apparent power
kVA
single
267
Total power factor (total kw / total kva)
Ratio
single
273
Current, average of 3 phases
Amp
single
275
Real power phase A
kW
single
277
Real power phase B
kW
single
279
Real power phase C
kW
single
281
Power factor phase A
Ratio
single
283
Power factor phase B
Ratio
single
285
Power factor phase C
Ratio
single
287
Voltage, phase A B
Volt
single
289
Voltage, phase B C
Volt
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Veris (E51) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
1
Real energy (diet import-export)
kWh
dword
3
Real energy (Q1-4 import)
kWh
dword
5
Real energy (Q2-3 import)
kWh
dword
7
Reactive energy Q1
kVARh
dword
9
Reactive energy Q2
kVARh
dword
11
Reactive energy Q3
kVARh
dword
13
Reactive energy Q4
kVARh
dword
15
Apparent energy: net (import export)
kVAh
integer
17
Apparent: Q1-4 import
kVAh
dword
19
Apparent: Q2-3 import
kVAh
dword
21
Total instantaneous real power
kW
smallint
22
Total instantaneous reactive power
kVAR
smallint
23
Total instantaneous apparent power
KVA
word
24
Total power factor (total kw /total kva)
Ratio
smallint
25
Voltage L-L, average of active phases
yolt
word
27
Current, average of active phases
Amp
word
28
Frequency
Hz
word
29
Total real power present demand
kW
smallint
30
Total reactive power present demand
kVAR
smallint
31
Total apparent power present demand
KVA
smallint
32
Total real power max. demand
kW
smallint
33
Total reactive power max. demand
kVAR
smallint
34
Total apparent power max. demand
KVA
smallint
35
Total real power max. demand
kW
smallint
36
Total reactive power max. demand
kVAR
smallint
37
Total apparent power max. demand
KVA
smallint
39
Pulse counter 1 (import real energy)
 
dword
41
Pulse counter 2 (export real energy)
 
dword
43
Accumulated real energy, phase A
kWh
dword
45
Accumulated real energy, phase B
kWh
dword
47
Accumulated real energy, phase C
kWh
dword
49
Accumulated real energy, phase A
kWh
dword
51
Accumulated real energy, phase B
kWh
dword
53
Accumulated real energy, phase C
kWh
dword
55
Accumulated Q1 reactive energy phase A
kVARh
dword
57
Accumulated Q1 reactive energy phase B
kVARh
dword
59
Accumulated Q1 reactive energy phase C
kVARh
dword
61
Accumulated Q2 reactive energy phase A
kVARh
dword
63
Accumulated Q2 reactive energy phase B
kVARh
dword
65
Accumulated Q2 reactive energy phase C
kVARh
dword
67
Accumulated Q3 reactive energy phase A
kVARh
dword
69
Accumulated Q3 reactive energy phase B
kVARh
dword
71
Accumulated Q3 reactive energy phase C
kVARh
dword
73
Accumulated Q4 reactive energy phase A
kYARh
dword
75
Accumulated Q4 reactive energy phase B
kVARh
dword
77
Accumulated Q4 reactive energy phase C
kVARh
dword
79
Accumulated apparent energy, phase A
kVAh
dword
81
Accumulated apparent energy, phase B
kYAh
dword
83
Accumulated apparent energy, phase C
kYAh
dword
85
Accumulated apparent energy, phase A
kYAh
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

Veris (H8035,H8036) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
256
Energy consumption
KWH
single
258
Energy onsumption (same 40257)
KWH
single
260
Real power
KW
single
262
Reactive power
VAR
single
264
Apparent power
YA
single
266
Power fator
 
single
268
Voltage, line to line
VOLTS
single
270
Voltage, line to neutral
VOLTS
single
272
Current
AMPS
single
274
Real power, phase A
KW
single
276
Real power, phase B
KW
single
278
Deal power, phase C
KW
single
280
Power factor, phase A
 
single
282
Power factor, phase B
 
single
284
Power factor, phase C
 
single
286
Voltage, phase A B
VOLTS
single
288
Voltage, phase B C
YOLTS
single
290
Voltage, phase A C
VOLTS
single
292
Yoltage, phase A N
VOLTS
single
294
Voltage, phase B N
VOLTS
single
296
Voltage, phase C N
VOLTS
single
298
Current, phase A
AMPS
single
300
Current, phase B
AMPS
single
302
Current, phase C
AMPS
single
304
Average real power
KW
single
306
Minimum real power
KW
single
308
Maximum real power
KW
single

Related MODBUS registers maps