bg

Saci MODBUS logger. Registers Map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Saci logger and read.

Saci (AHM1) - Mapping

MODBUS offset
Description
Units
Data type
6
V1
V
single
8
V2
V
single
10
V3
V
single
12
V12
V
single
14
V23
V
single
16
V31
V
single
18
I1
A
single
20
I2
A
single
22
I3
A
single
24
In (3P4W)
A
single
26
P1
kW
single
28
P2
kW
single
30
P3
kW
single
32
P
kW
single
34
Q1
kvar
single
36
Q2
kvar
single
38
Q3
kvar
single
40
Q
kvar
single
42
S1
kVA
single
44
S2
kVA
single
46
S3
kVA
single
48
S
kVA
single
50
PF1
 
single
52
PF2
 
single
54
PF3
 
single
56
PF
 
single
58
F
Hz
single
60
Average value of vph-N
V
single
62
Average value of vph-ph
V
single
64
Average current
A
single
66
Import active energy
kWh
single
68
Export active energy
kWh
single
70
Import reactive energy
kvarh
single
72
Export reactive energy
kvarh
single
74
Apparent energy
kVAh
single
76
1st quadrant reactive energy - EQL+
kvarh
single
78
2nd quadrant reactive energy - EQC+
kvarh
single
80
3rd quadrant reactive energy - EQL-
kvarh
single
82
4th quadrant reactive energy - EQC-
kvarh
single
84
Hour meter - EP+
s
single
86
Hour meter - EP-
s
single
88
Alternative import active energy
kWh
single
90
Alternative export active energy
kWh
single
92
Alternative import reactive energy
kvarh
single
94
Alternative export reactive energy
kvarh
single
96
Alternative apparent energy
kVAh
single
98
Alternative energy - EQL+
kvarh
single
100
Alternative energy - EQC+
kvarh
single
102
Alternative energy - EQL-
kvarh
single
104
Alternative energy - EQC-
kvarh
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Saci (ANG96) - Mapping

MODBUS offset
Description
Units
Data type
2
Voltage
V
single
4
Current L1
A
single
6
THD% current L1
%
single
8
THD% voltage
%
single
16
Active power L1
KW
single
18
Power factor
 
single
20
Reactive power L1
Kvar
single
22
Apparent power L1
KVA
single
24
Voltage
V
single
32
Voltage
V
single
34
Current L2
A
single
36
THD% current L2
%
single
38
THD% voltage
%
single
40
Active power L2
KW
single
48
Power factor
 
single
50
Reactive power L2
Kvar
single
52
Apparent power L2
KVA
single
54
Voltage
V
single
56
Voltage
V
single
64
Current L3
A
single
66
THD% current L3
%
single
68
THD% voltage
%
single
70
Active power L3
KW
single
72
Power factor
 
single
80
Reactive power L3
Kvar
single
82
Apparent power L3
KVA
single
84
Neutral current
A
single
86
Frequency
Hz
single
88
Power factor
 
single
96
Apparent power total
KVA
single
98
Active power total
KW
single
100
Reactive power total
Kvar
single
102
Import active energy
kWh
single
104
Export active energy
kWh
single
112
Reactive energy. inductive
kvarh
single
114
Reactive energy. capacitive
kvarh
single
116
Generator mode. import active energy
kWh
single
118
Generator mode. export active energy
kWh
single
120
Generator mode. reactive energy. inductive
kvarh
single
128
Generator mode. reactive energy. capacitive
kvarh
single
130
Import active energy time counter
 
dword
132
Export active energy time counter
 
dword
134
Generator mode. import active energy time counter
 
dword
136
Generator model. export active energy time counter
 
dword
256
Current L1
A
single
258
Current L1
A
single
260
Current L2
A
single
262
Current L2
A
single
264
Current L3
A
single
272
Current L3
A
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Saci (M2DL2) - MODBUS Registers

MODBUS offset
Description
Units
Data type
8
Export active energy accumulator
kWh
dword
10
Import active energy accumulator
kWh
dword
12
Voltage
V
word
13
Current
A
word
14
Active power
W
word
15
Reactive power
W
word
16
Power factor
 
word
17
Frequency
Hz
word
256
Import reactive energy accumulator Q1 + Q2
kWh
dword
258
Export reactive energy accumulator Q3 + Q4
kWh
dword
260
Q1 reactive energy accumulator
kWh
dword
262
Q2 reactive energy accumulator
kWh
dword
264
Q3 reactive energy accumulator
kWh
dword
266
Q4 reactive energy accumulator
kWh
dword

Saci (TCIL2) - Mapping

MODBUS offset
Description
Units
Data type
86
Total power factor
 
single
88
Grid frequency
Hz
single
96
Average value of three phase voltages
V
single
98
Average value of three line voltages
V
single
100
Average value of three phase currents
A
single
102
EP+
kWh
single
104
EP-
kWh
single
112
EQ+
kvarh
single
114
EQ-
kvarh
single
116
Apparent energy
kVAh
single
118
Trip energy
KWh
single
120
First-quadrant reactive energy EQL+
kvarh
single
128
Second-quadrant reactive energy EQC+
kvarh
single
130
Third-quadrant reactive energy EQL-
kvarh
single
132
Four-quadrant reactive energy EQC-
kvarh
single
134
Import active energy[total
kWh
single
136
Import active energy[tip
kWh
single
144
Import active energy[peak
kWh
single
146
Import active energy[flat
kWh
single
148
Import active energy[valley
kWh
single
150
Export active energy[total
kWh
single
152
Export active energy[tip
kWh
single
256
Export active energy[peak
kWh
single
258
Export active energy[flat
kWh
single
260
Export active energy[valley
kWh
single
262
Import active energy of this month[total
kWh
single
264
Import active energy of this month[tip
kWh
single
272
Import active energy of this month[peak
kWh
single
274
Import active energy of this month[flat
kWh
single
276
Import active energy of this month[valley
kWh
single
278
Export active energy of this month[total
kWh
single
280
Export active energy of this month[tip
kWh
single
288
Export active energy of this month[peak
kWh
single
290
Export active energy of this month[flat
kWh
single
292
Export active energy of this month[valley
kWh
single
294
Import active energy of last month[total
kWh
single
296
Import active energy of last month[tip
kWh
single
304
Import active energy of last month[peak
kWh
single
306
Import active energy of last month[flat
kWh
single
308
Import active energy of last month[valley
kWh
single
310
Export active energy of last month[total
kWh
single
312
Export active energy of last month[tip
kWh
single
320
Export active energy of last month[peak
kWh
single
322
Export active energy of last month[flat
kWh
single
324
Export active energy of last month[valley
kWh
single
326
Import active energy two month before[total
kWh
single
328
Import active energy two month before[tip
kWh
single
336
Import active energy two month before[peak
kWh
single
338
Import active energy two month before[flat
kWh
single
340
Import active energy two month before[valley
kWh
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.