Meatrol MODBUS logging. Registers Map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Meatrol logging and capture.

Meatrol (ME237) - MODBUS Registers

MODBUS offset
Description
Units
Data type
1000
Voltage value of phase A
V
single
1002
Voltage value of phase B
V
single
1004
Voltage value of phase C
V
single
1006
Average phase voltage value
V
single
1008
Voltage value of line A-B
V
single
1010
Voltage value of line B-C
V
single
1012
Voltage value of line C-A
V
single
1014
Average line voltage value
V
single
1016
Current value of phase A
A
single
1018
Current value of phase B
A
single
1020
Current value of phase C
A
single
1022
Average value of three-phase current
A
single
1026
Active power of phase A
W
single
1028
Active power of phase B
W
single
1030
Active power of phase C
W
single
1032
Sum of three-phase active power
W
single
1034
Reactive power of phase A
Var
single
1036
Reactive power of phase B
Var
single
1038
Reactive power of phase C
Var
single
1040
Sum of three-phase reactive power
Var
single
1042
Apparent power of phase A
Va
single
1044
Apparent power of phase B
Va
single
1046
Apparent power of phase A
Va
single
1048
Sum of three-phase apparent power
Va
single
1050
Power factor of phase A
 
single
1052
Power factor of phase B
 
single
1054
Power factor of phase C
 
single
1056
Average power factor
 
single
1058
Fundamental power factor of phase A
 
single
1060
Fundamental power factor of phase B
 
single
1062
Fundamental power factor of phase C
 
single
1064
Average fundamental power factor
 
single
1066
Grid frequency
Hz
single
2000
Percentage of total harmonic of voltage of phase A
%
single
2002
Percentage of total harmonic of voltage of phase B
%
single
2004
Percentage of total harmonic of voltage of phase A
%
single
2006
Three phase voltage total harmonic percentage average
%
single
2008
Percentage of total harmonic current of phase A
%
single
2010
Percentage of total harmonic current of phase B
%
single
2012
Percentage of total harmonic current of phase C
%
single
2014
Percentage average value of total harmonic of three-phase current
%
single
4000
Positive active energy of phase A
0.1kWh
dword
4002
Positive active energy of phase B
0.1kWh
dword
4004
Positive active energy of phase C
0.1kWh
dword
4006
Sum of three-phase positive active energy
0.1kWh
dword
4008
Reverse active electric energy of phase A
0.1kWh
dword
4010
Reverse active electric energy of phase B
0.1kWh
dword
4012
Reverse active electric energy of phase C
0.1kWh
dword
4014
Sum of three-phase reverse active energy
0.1kWh
dword
4024
Positive reactive energy of phase A
0.1kVarh
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

Meatrol (ME437) - MODBUS Registers

MODBUS offset
Description
Units
Data type
2000
Phase 1 power factor
 
single
2002
Phase 2 power factor
 
single
2004
Phase 3 power factor
 
single
2006
Average of PF1, PF2, PF3
 
single
2008
Phase 1 displacement power factor
 
single
2010
Phase 2 displacement power factor
 
single
2012
Phase 3 displacement power factor
 
single
2014
Average of DPF1, DPF2, DPF3
 
single
2016
Phase 1 frequency
Hz
single
2018
Phase 2 frequency
Hz
single
2020
Phase 3 frequency
Hz
single
2022
Average of freq1, freq2, freq3
Hz
single
2024
Range:2-52
 
word
2025
Range:2-52
 
word
2026
Range:2-52
 
word
2027
Phase 1 X times harmonics current distortion
%
single
2029
Phase 2 X times harmonics current
%
single
2031
Phase 3 X times harmonics current distortion
%
single
2033
Average of I1THDx, I2THDx, I3THDx
%
single
2035
Phase 1 y times harmonics current distortion
%
single
2037
Phase 2 y times harmonics current distortion
%
single
2039
Phase 3 y times harmonics current distortion
%
single
2041
Average of U1THDy, U2THDy, U3THDy
%
single
2043
Phase 1 z times harmonics current distortion
%
single
2045
Phase 2 z times harmonics current distortion
%
single
2047
Phase 3 z times harmonics current distortion
%
single
2049
Average of U1THDz, U2THDz, U3THDz
%
single
2051
Phase 1 total harmonics current distortion
%
single
2053
Phase 2 total harmonics current distortion
%
single
2055
Phase 3 total harmonics current distortion
%
single
2057
Average of U1THD, U2THD, U3THD
%
single
2059
Phase 1 x times harmonics current
V
single
2061
Phase 2 x times harmonics current
V
single
2063
Phase 3 x times harmonics current
V
single
2065
Average of U1THx, U2THx, U3THx
V
single
2067
Phase 1 y times harmonics current
V
single
2069
Phase 2 y times harmonics current
V
single
2071
Phase 3 y times harmonics current
V
single
2073
Average of U1THy, U2THy, U3THy
V
single
2075
Phase 1 z times harmonics current
V
single
2077
Phase 2 z times harmonics current
V
single
2079
Phase 3 z times harmonics current
V
single
2081
Average of U1THz, U2THz, U3THz
V
single
2083
Phase 1 X times harmonics voltage distortion
%
single
2085
Phase 2 X times harmonics voltage distortion
%
single
2087
Phase 3 X times harmonics voltage
%
single
2089
Average of U1THDx, U2THDx, U3THDx
%
single
2091
Phase 1 y times harmonics voltage distortion
%
single
2093
Phase 2 y times harmonics voltage distortion
%
single
2095
Phase 3 y times harmonics voltage distortion
%
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Meatrol (ME631) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
2000
Phase 1 power factor
 
single
2002
Phase 2 power factor
 
single
2004
Phase 3 power factor
 
single
2006
Average of PF1, PF2, PF3
 
single
2008
Phase 1 displacement power factor
 
single
2010
Phase 2 displacement power factor
 
single
2012
Phase 3 displacement power factor
 
single
2014
Average of DPF1, DPF2, DPF3
 
single
2016
Phase 1 frequency
Hz
single
2018
Phase 2 frequency
Hz
single
2020
Phase 3 frequency
Hz
single
2022
Average of freq1, freq2, freq3
Hz
single
2024
Range:2-52
 
word
2025
Range:2-52
 
word
2026
Range:2-52
 
word
2027
Phase 1 X times harmonics current distortion
%
single
2029
Phase 2 X times harmonics current distortion
%
single
2031
Phase 3 X times harmonics current distortion
%
single
2033
Average of I1THDx, I2THDx, I3THDx
%
single
2035
Phase 1 y times harmonics current distortion
%
single
2037
Phase 2 y times harmonics current
%
single
2039
Phase 3 y times harmonics current distortion
%
single
2041
Average of U1THDy, U2THDy, U3THDy
%
single
2043
Phase 1 z times harmonics current distortion
%
single
2045
Phase 2 z times harmonics current distortion
%
single
2047
Phase 3 z times harmonics current distortion
%
single
2049
Average of U1THDz, U2THDz, U3THDz
%
single
2051
Phase 1 total harmonics current distortion
%
single
2053
Phase 2 total harmonics current distortion
%
single
2055
Phase 3 total harmonics current distortion
%
single
2057
Average of U1THD, U2THD, U3THD
%
single
2059
Phase 1 x times harmonics current
V
single
2061
Phase 2 x times harmonics current
V
single
2063
Phase 3 x times harmonics current
V
single
2065
Average of U1THx, U2THx, U3THx
V
single
2067
Phase 1 y times harmonics current
V
single
2069
Phase 2 y times harmonics current
V
single
2071
Phase 3 y times harmonics current
V
single
2073
Average of U1THy, U2THy, U3THy
V
single
2075
Phase 1 z times harmonics current
V
single
2077
Phase 2 z times harmonics current
V
single
2079
Phase 3 z times harmonics current
V
single
2081
Average of U1THz, U2THz, U3THz
V
single
2083
Phase 1 X times harmonics voltage distortion
%
single
2085
Phase 2 X times harmonics voltage distortion
%
single
2087
Phase 3 X times harmonics voltage distortion
%
single
2089
Average of U1THDx, U2THDx, U3THDx
%
single
2091
Phase 1 y times harmonics voltage distortion
%
single
2093
Phase 2 y times harmonics voltage distortion
%
single
2095
Phase 3 y times harmonics voltage
%
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Meatrol (MP440) - MODBUS Registers

MODBUS offset
Description
Units
Data type
99
0 = direct connect 1 = VT
 
word
102
=realvalue*1000
V
dword
1000
Current phase A
A
single
1002
Current phase B
A
single
1004
Current phase C
A
single
1006
Current phase N
A
single
1008
Average of IA, IB, IC
A
single
1010
Voltage UA-UN
V
single
1012
Voltage UB-UN
V
single
1014
Voltage UC-UN
V
single
1016
Voltage UN-UE
V
single
1018
Average of UA, UB, UC
V
single
1020
Voltage UA-UB
V
single
1022
Voltage UB-UC
V
single
1024
Voltage UC-UA
V
single
1026
Average of UAB, UBC, UCA
V
single
1028
Active power phase A
kW
single
1030
Active power phase B
kW
single
1032
Active power phase C
kW
single
1034
Total active power
kW
single
1036
Reactive power phase A
kVAR
single
1038
Reactive power phase B
kVAR
single
1040
Reactive power phase C
kVAR
single
1042
Total reactive power
kVAR
single
1044
Apparent power phase A
kVA
single
1046
Apparent power phase B
kVA
single
1048
Apparent power phase C
kVA
single
1050
Total apparent power
kVA
single
1052
Power factor phase A
 
single
1054
Power factor phase B
 
single
1056
Power factor phase C
 
single
1058
Total power factor
 
single
1060
Displacement power factor phase A
 
single
1062
Displacement power factor phase B
 
single
1064
Displacement power factor phase C
 
single
1066
Total displacement power factor
 
single
1068
Frequency phase A
Hz
single
1070
Frequency phase B
Hz
single
1072
Frequency phase C
Hz
single
1074
Average of FreqA, FreqB, FreqC
Hz
single
2000
Active energy import phase A
kWh
dword
2002
Active energy import phase B
kWh
dword
2004
Active energy import phase C
kWh
dword
2006
Total active energy import phase all
kWh
dword
2008
Active energy export phase A
kWh
dword
2010
Active energy export phase B
kWh
dword
2012
Active energy export phase C
kWh
dword
2014
Total active energy export phase all
kWh
dword
2016
Reactive energy import phase A
kVARh
dword
2018
Reactive energy import phase B
kVARh
dword
There are more MODBUS items for this device. Please download the program to discover all registers.