bg

IME MODBUS data logging. Registers Map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable IME data logging and record.

IME (Conto D2) - MODBUS Registers

MODBUS offset
Description
Units
Data type
8192
Voltage
V
dword
8194
Current
A
dword
8196
Active power
W
dword
8198
Sign of active power
 
word
8199
Power factor
 
word
8200
Sector of power factor (cap or ind)
 
word
8201
Frequency
Hz
word
8202
Positive active energy
kWh
dword
8204
Positive partial active energy
kWh
dword
8206
Operating time counter
sec.
dword
200
Reset bit to bit defined
 
word
768
Device identifier
 
word

IME (Nemo 72) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
4096
Phase 1 : phase voltage
V
dword
4098
Phase 2 : phase voltage
V
dword
4100
Phase 3 : phase voltage
V
dword
4102
Phase 1 : current
A
dword
4104
Phase 2 : current
A
dword
4106
Phase 3 : current
A
dword
4108
Neutral current
A
dword
4110
Chained voltage : L1 L2
V
dword
4112
Chained voltage : L2 L3
V
dword
4114
Chained voltage : L3 L1
V
dword
4116
3 phase : active power
W/var/VA
dword
4118
3 phase : reactive power
W/var/VA
dword
4120
3 phase : apparent power
W/var/VA
dword
4122
3 phase : sign of active power
 
word
4123
3 phase : sign of reactive power
 
word
4124
3 phase : positive active energy
Wh
dword
4126
3 phase : positive reactive energy
Wh
dword
4128
3 phase : negative active energy
Wh
dword
4130
3 phase : negative reactive energy
Wh
dword
4132
3 phase : power factor
s
smallint
4133
3 phase : sector of power factor (cap or ind)
a
word
4134
Frequency
Hz
word
4135
3 phase : average power
W/var/VA
dword
4137
3 phase : peak maximum demand
W/var/VA
dword
4139
Time counter for average power
minutes
word
4140
Phase 1 : active power
W/var/VA
dword
4142
Phase 2 : active power
W/var/VA
dword
4144
Phase 3 : active power
W/var/VA
dword
4146
Phase 1 : sign of active power
 
word
4147
Phase 2 : sign of active power
 
word
4148
Phase 3 : sign of active power
 
word
4149
Phase 1 : reactive power
W/var/VA
dword
4151
Phase 2 : reactive power
W/var/VA
dword
4153
Phase 3 : reactive power
W/var/VA
dword
4155
Phase 1 : sign of reactive power
 
word
4156
Phase 2 : sign of reactive power
 
word
4157
Phase 3 : sign of reactive power
 
word
4158
Phase 1 : apparent power
W/var/VA
dword
4160
Phase 2 : apparent power
W/var/VA
dword
4162
Phase 3 : apparent power
W/var/VA
dword
4164
Phase 1 : power factor
s
smallint
4165
Phase 2 : power factor
s
smallint
4166
Phase 3 : power factor
s
smallint
4167
Phase 1 : power factor sector
a
word
4168
Phase 2 : power factor sector
a
word
4169
Phase 3 : power factor sector
a
word
4170
Phase 1 : thd V1
%
word
4171
Phase 2 : thd V2
%
word
4172
Phase 3 : thd V3
%
word
4173
Phase 1 : thd I1
%
word
There are more MODBUS items for this device. Please download the program to discover all registers.

IME (Nemo 96) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
769
Phase 1 : phase voltage
V
dword
773
Phase 2 : phase voltage
V
dword
777
Phase 3 : phase voltage
V
dword
781
Phase 1 : current
A
dword
785
Phase 2 : current
A
dword
789
Phase 3 : current
A
dword
793
3 phase : active power
W/var/VA
dword
797
3 phase : reactive power
W/var/VA
dword
801
3 phase : apparent power
W/var/VA
dword
805
3 phase : positive active energy
Wh
dword
809
Chained voltage : L1 L2
V
dword
813
Chained voltage : L2 L3
V
dword
817
Chained voltage : L3 L1
V
dword
821
3 phase : negative active energy
Wh
dword
825
Frequency
Hz
word
827
Operating timer counter
 
word
829
3 phase : power factor
 
word
831
3 phase : sector of power factor (cap or ind)
a
word
832
Voltages sequence diagnostic
 
word
833
Output relay status
(2)
word
835
3 phase : positive reactive energy
Wh
dword
839
3 phase : sign of active power
(5)
word
840
3 phase : negative reactive energy
Wh
dword
844
3 phase : sign of reactive power
(5)
word
848
3 phase : average power
W/var/VA
dword
852
3 phase : peak maximum demand
W/var/VA
dword
856
Time counter for average power
minutes
word
857
Neutral current
A
dword
861
Phase 1 : active power
W/var/VA
dword
865
Phase 2 : active power
W/var/VA
dword
869
Phase 3 : active power
W/var/VA
dword
873
Phase 1 : sign of active power
(5)
word
874
Phase 2 : sign of active power
(5)
word
875
Phase 3 : sign of active power
(5)
word
876
Phase 1 : reactive power
W/var/VA
dword
880
Phase 2 : reactive power
W/var/VA
dword
884
Phase 3 : reactive power
W/var/VA
dword
888
Phase 1 : sign of reactive power
(5)
word
889
Phase 2 : sign of reactive power
(5)
word
890
Phase 3 : sign of reactive power
(5)
word
891
Phase 1 : apparent power
W/var/VA
dword
895
Phase 2 : apparent power
W/var/VA
dword
899
Phase 3 : apparent power
W/var/VA
dword
903
Phase 1 : power factor
 
word
905
Phase 2 : power factor
 
word
907
Phase 3 : power factor
 
word
909
Phase 1 : power factor sector
a
word
910
Phase 2 : power factor sector
a
word
911
Phase 3 : power factor sector
a
word
912
Phase 1 : thd V1
%
word
There are more MODBUS items for this device. Please download the program to discover all registers.

IME (Nemo D4-DC) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
4096
Voltage
V
dword
4098
Current
A
dword
4100
Signed power
 
dword
4102
Positive energy
 
dword
4104
Negative energy
 
dword
4106
Time
s
dword
4108
Average power
 
dword
4110
Maximum power demand
 
dword
4112
Minutes elapsed durino the average calculation
 
word
4114
Positive amperehours
Ah
dword
4116
Negative amperehours
Ah
dword
4609
Current transformer ratio (kta)
 
word
4610
Voltage transformer ratio (ktv)
 
word
4611
Device identifier
 
word

IME (Nemo D4-LE) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
4096
Phase 1 : phase voltage
V
dword
4098
Phase 2 : phase voltage
V
dword
4100
Phase 3 : phase voltage
V
dword
4102
Phase 1 : current
A
dword
4104
Phase 2 : current
A
dword
4106
Phase 3 : current
A
dword
4108
Neutral current
A
dword
4110
Chained voltage : L1 L2
V
dword
4112
Chained voltage : L2 L3
V
dword
4114
Chained voltage : L3 L1
V
dword
4116
3 phase : active power
W/var/VA
dword
4118
3 phase : reactive power
W/var/VA
dword
4120
3 phase : apparent power
W/var/VA
dword
4122
3 phase : sign of active power
 
word
4123
3 phase : sign of reactive power
 
word
4124
3 phase : positive active energy
Wh
dword
4126
3 phase : positive reactive energy
Wh
dword
4128
3 phase : negative active energy
Wh
dword
4130
3 phase : negative reactive energy
Wh
dword
4132
3 phase : power factor
s
smallint
4133
3 phase : sector of power factor (cap or ind)
a
word
4134
Frequency
Hz
word
4135
3 phase : average power
W/var/VA
dword
4137
3 phase : peak maximum demand
W/var/VA
dword
4139
Time counter for average power
minutes
word
4140
Phase 1 : active power
W/var/VA
dword
4142
Phase 2 : active power
W/var/VA
dword
4144
Phase 3 : active power
W/var/VA
dword
4146
Phase 1 : sign of active power
 
word
4147
Phase 2 : sign of active power
 
word
4148
Phase 3 : sign of active power
 
word
4149
Phase 1 : reactive power
W/var/VA
dword
4151
Phase 2 : reactive power
W/var/VA
dword
4153
Phase 3 : reactive power
W/var/VA
dword
4155
Phase 1 : sign of reactive power
 
word
4156
Phase 2 : sign of reactive power
 
word
4157
Phase 3 : sign of reactive power
 
word
4158
Phase 1 : apparent power
W/var/VA
dword
4160
Phase 2 : apparent power
W/var/VA
dword
4162
Phase 3 : apparent power
W/var/VA
dword
4164
Phase 1 : power factor
s
smallint
4165
Phase 2 : power factor
s
smallint
4166
Phase 3 : power factor
s
smallint
4167
Phase 1 : power factor sector
a
word
4168
Phase 2 : power factor sector
a
word
4169
Phase 3 : power factor sector
a
word
4170
Phase 1 : thd V1
%
word
4171
Phase 2 : thd V2
%
word
4172
Phase 3 : thd V3
%
word
4173
Phase 1 : thd I1
%
word
There are more MODBUS items for this device. Please download the program to discover all registers.

IME (Nemo D4-LP) - MODBUS Registers

MODBUS offset
Description
Units
Data type
769
Phase 1 : phase voltage
V
dword
773
Phase 2 : phase voltage
V
dword
777
Phase 3 : phase voltage
V
dword
781
Phase 1 : current
A
dword
785
Phase 2 : current
A
dword
789
Phase 3 : current
A
dword
793
3 phase : active power
W/var/VA
dword
797
3 phase : reactive power
W/var/VA
dword
801
3 phase : apparent power
W/var/VA
dword
805
3 phase : positive active energy
Wh
dword
809
Chained voltage : L1 L2
V
dword
813
Chained voltage : L2 L3
V
dword
817
Chained voltage : L3 L1
V
dword
821
3 phase : partial positive active energy
Wh
dword
825
Frequency
Hz
word
829
3 phase : power factor
 
word
831
3 phase : sector of power factor (cap or ind)
(1)
word
835
3 phase : positive reactive energy
Wh
dword
839
3 phase : sign of active power
(5)
word
840
Time counter
s
dword
844
3 phase : sign of reactive power
(5)
word
848
3 phase : average power
W/var/VA
dword
852
3 phase : peak maximum demand
W/var/VA
dword
856
Time counter for average power
minutes
word
857
Neutro current
A
dword
861
Phase 1 : active power
W/var/VA
dword
865
Phase 2 : active power
W/var/VA
dword
869
Phase 3 : active power
W/var/VA
dword
873
Phase 1 : sign of active power
(5)
word
874
Phase 2 : sign of active power
(5)
word
875
Phase 3 : sign of active power
(5)
word
876
Phase 1 : reactive power
W/var/VA
dword
880
Phase 2 : reactive power
W/var/VA
dword
884
Phase 3 : reactive power
W/var/VA
dword
888
Phase 1 : sign of reactive power
(5)
word
889
Phase 2 : sign of reactive power
(5)
word
890
Phase 3 : sign of reactive power
(5)
word
891
Phase 1 : average current
A
dword
895
Phase 2 : average current
A
dword
899
Phase 3 : average current
A
dword
903
Phase 1 : current maximum demand
A
dword
907
Phase 2 : current maximum demand
A
dword
911
Phase 3 : current maximum demand
A
dword
915
Phase 1 : thd voltage
%
word
917
Phase 2 : thd voltage
%
word
919
Phase 3 : thd voltage
%
word
921
Phase 1 : thd current
%
word
922
Phase 2 : thd current
%
word
924
Phase 3 : thd current
%
word
200
Reset (r/w) bit to bit defined
(6)
word
There are more MODBUS items for this device. Please download the program to discover all registers.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.