bg

Elspec MODBUS data logger. Registers Map


The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable Elspec data logger and read.

Elspec (EQC ACR) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
8448
Fault
 
single
16
Frequency
 
single
2
Voltage L2
 
single
4
Voltage L3
 
single
6
Voltage
 
single
8
Voltage L12
 
single
10
Voltage L23
 
single
12
Voltage L31
 
single
14
Voltage
 
single
20
Current L1 (mains)
 
single
22
Current L2 (mains)
 
single
24
Current L3 (mains)
 
single
26
Current (mains)
 
single
28
Current L1 (caps)
 
single
30
Current L2 (caps)
 
single
32
Current L3 (caps)
 
single
34
Current (caps)
 
single
36
Current L1 (load)
 
single
38
Current L2 (load)
 
single
40
Current L3 (load)
 
single
42
Current (load)
 
single
50
Active power L1 (mains)
 
single
52
Active power L2 (mains)
 
single
54
Active power L3 (mains)
 
single
56
Active power L3 (mains)
 
single
58
Reactive power L1 (mains)
 
single
60
Reactive power L2 (mains)
 
single
62
Reactive power L3 (mains)
 
single
64
Reactive power L3 (mains)
 
single
66
Apparent power L1 (mains)
 
single
68
Apparent power L2 (mains)
 
single
70
Apparent power L3 (mains)
 
single
72
Apparent power L3 (mains)
 
single
88
Reactive power L1 (caps)
 
single
90
Reactive power L2 (caps)
 
single
92
Reactive power L3 (caps)
 
single
94
Reactive power L3 (caps)
 
single
110
Active power L1 (load)
 
single
112
Active power L2 (load)
 
single
114
Active power L3 (load)
 
single
116
Active power L3 (load)
 
single
118
Reactive power L1 (load)
 
single
120
Reactive power L2 (load)
 
single
122
Reactive power L3 (load)
 
single
124
Reactive power L3 (load)
 
single
126
Apparent power L1 (load)
 
single
128
Apparent power L2 (load)
 
single
130
Apparent power L3 (load)
 
single
132
Apparent power L3 (load)
 
single
140
Power factor (mains)
 
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Elspec (G4400) - MODBUS Registers

MODBUS offset
Description
Units
Data type
543
Compliance name (EN 50160 or any other compliance standard)
String
string
563
Compliance description
String
string
603
OK / fail / NA status of the compliance currently running
UINT16
word
621
Percentage from the entire time (including off time) in which this compliance parameters was ok
float
single
623
Percentage from the entire time (including off time) in which this the compliance parameter was not ok
float
single
625
Percentage from the entire time (including off time) in which this compliance parameter was not evaluated (due to device off time)
float
single
627
Number of compliance parameters under check
UINT32
dword
537
Power supply temperature (read every second)
float
single
999
The measured frequency , calculated every 200 msec (10/12 cycles)
float
single
1025
Line 1 active power (W), calculate every cycle
float
single
1027
Line 2 active power (W), calculate every cycle
float
single
1029
Line 3 active power (W), calculate every cycle
float
single
1037
Total active power (W), calculate every cycle
float
single
1041
Line 1 reactive power (VAr) calculate every cycle
float
single
1043
Line 2 reactive power (VAr) calculate every cycle
float
single
1045
Line 3 reactive power (VAr) calculate every cycle
float
single
1053
Reactive power - total (VAr) calculate every cycle
float
single
1057
Line 1 apparent power (VA) calculate every cycle
float
single
1059
Line 2 apparent power (VA) calculate every cycle
float
single
1061
Line 3 apparent power (VA) calculate every cycle
float
single
1069
Apparent power total (VA) calculate every cycle
float
single
1103
RMS voltage V1, calculate every cycle
float
single
1105
RMS voltage V2, calculate every cycle
float
single
1107
RMS voltage V3, calculate every cycle
float
single
1109
RMS voltage V12, calculate every cycle
float
single
1111
RMS voltage V23, calculate every cycle
float
single
1113
RMS voltage V31, calculate every cycle
float
single
1117
RMS voltage I1, calculate every cycle
float
single
1119
RMS voltage I2, calculate every cycle
float
single
1121
RMS current I3, calculate every cycle
float
single
1123
Cycle by cycle average RMS voltage
float
single
1125
Cycle by cycle average RMS phase to phase voltage
float
single
1127
Cycle by cycle average RMS current
float
single
1159
Internal DSP temperature, read every cycle
float
single
1161
External DSP temperature (PT100 READING) , read every cycle
float
single
1659
PST (short term flicker) - L1 - calculated over 2 seconds
float
single
1661
PST (short term flicker) - L1 - calculated over 2 seconds
float
single
1663
PST (short term flicker) - L1 - calculated over 2 seconds
float
single
1665
PST (short term flicker)- L12 - calculated over 2 seconds
float
single
1667
PST (short term flicker)- L23 -calculated over 2 seconds
float
single
1669
PST (short term flicker)- L31 - calculated over 2 seconds
float
single
1671
PST (short term flicker) - L1 - calculated over 10 seconds
float
single
1673
PST (short term flicker)- L2 - calculated over 10 seconds
float
single
1675
PST (short term flicker)- L3 - calculated over 10 seconds
float
single
1677
PST (short term flicker)- L12 - calculated over 10 seconds
float
single
1679
PST (short term flicker)- L23 - calculated over 10 seconds
float
single
1681
PST (short term flicker)- L31 - calculated over 10 seconds
float
single
1683
PST (short term flicker)- L1 - calculated over 10 minutes
float
single
1685
PST (short term flicker)- L2 - calculated over 10 minutes
float
single
1687
PST (short term flicker)- L3 - calculated over 10 minutes
float
single
There are more MODBUS items for this device. Please download the program to discover all registers.