ABB MODBUS logging. Registers Map
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These tools provide continuous and reliable ABB logging and capture.
ABB (-3P81-) - MODBUS Registers
MODBUS offset
Description
Units
Data type
40071
Phase A Current
A
word
40072
Phase B Current
A
word
40073
Phase C Current
A
word
40074
Scale factor [A_SF]
smallint
40075
Phase Voltage AB
V
word
40076
Phase Voltage BC
V
word
40077
Phase Voltage CA
V
word
40078
Phase Voltage AN
V
word
40079
Phase Voltage BN
V
word
40080
Phase Voltage CN
V
word
40081
Scale factor [V_SF]
smallint
40083
Scale factor [W_SF]
smallint
40084
Line Frequency
Hz
word
40085
Scale factor [HZ_SF]
smallint
40086
AC Apparent Power
VA
smallint
40087
Scale factor [VA_SF]
smallint
40088
AC Reactive Power
var
smallint
40089
Scale factor [VAR_SF]
smallint
40090
AC Power Factor
Pct
smallint
40091
Scale factor [PF_SF]
smallint
40094
Scale factor [WH_SF]
smallint
40096
Scale factor [DCA_SF]
smallint
40098
Scale factor [DCV_SF]
smallint
40100
Scale factor [DCW_SF]
smallint
40101
Cabinet Temperature
C
smallint
40102
Heat Sink Temperature
C
smallint
40103
Transformer Temperature
C
smallint
40104
Other Temperature
C
smallint
40105
Scale factor [TMP_SF]
smallint
40106
Enumerated value. Operating state
word
40107
Vendor specific operating state code
word
40108
Bitmask value. Event fields
dword
40110
Reserved for future use
dword
40112
Vendor defined events
dword
40114
Vendor defined events
dword
40116
Vendor defined events
dword
40118
Vendor defined events
dword
40122
Type of DER device. Default value is 4 to indicate PV device.
word
40123
Continuous power output capability of the inverter.
W
word
40124
Scale factor
smallint
40125
Continuous Volt-Ampere capability of the inverter.
VA
word
40126
Scale factor
smallint
40127
Continuous VAR capability of the inverter in quadrant 1.
var
smallint
40128
Continuous VAR capability of the inverter in quadrant 2.
var
smallint
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB (3P86) - MODBUS Registers
MODBUS offset
Description
Units
Data type
40071
Phase A Current
A
word
40072
Phase B Current
A
word
40073
Phase C Current
A
word
40074
Scale factor [A_SF]
smallint
40075
Phase Voltage AB
V
word
40076
Phase Voltage BC
V
word
40077
Phase Voltage CA
V
word
40078
Phase Voltage AN
V
word
40079
Phase Voltage BN
V
word
40080
Phase Voltage CN
V
word
40081
Scale factor [V_SF]
smallint
40083
Scale factor [W_SF]
smallint
40084
Line Frequency
Hz
word
40085
Scale factor [HZ_SF]
smallint
40086
AC Apparent Power
VA
smallint
40087
Scale factor [VA_SF]
smallint
40088
AC Reactive Power
var
smallint
40089
Scale factor [VAR_SF]
smallint
40090
AC Power Factor
Pct
smallint
40091
Scale factor [PF_SF]
smallint
40094
Scale factor [WH_SF]
smallint
40096
Scale factor [DCA_SF]
smallint
40098
Scale factor [DCV_SF]
smallint
40100
Scale factor [DCW_SF]
smallint
40101
Cabinet Temperature
C
smallint
40102
Heat Sink Temperature
C
smallint
40103
Transformer Temperature
C
smallint
40104
Other Temperature
C
smallint
40105
Scale factor [TMP_SF]
smallint
40106
Enumerated value. Operating state
word
40107
Vendor specific operating state code
word
40108
Bitmask value. Event fields
dword
40110
Reserved for future use
dword
40112
Vendor defined events
dword
40114
Vendor defined events
dword
40116
Vendor defined events
dword
40118
Vendor defined events
dword
40122
Type of DER device. Default value is 4 to indicate PV device.
word
40123
Continuous power output capability of the inverter.
W
word
40124
Scale factor
smallint
40125
Continuous Volt-Ampere capability of the inverter.
VA
word
40126
Scale factor
smallint
40127
Continuous VAR capability of the inverter in quadrant 1.
var
smallint
40128
Continuous VAR capability of the inverter in quadrant 2.
var
smallint
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB (3P88) - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
40071
Phase A Current
A
word
40072
Phase B Current
A
word
40073
Phase C Current
A
word
40074
Scale factor [A_SF]
smallint
40075
Phase Voltage AB
V
word
40076
Phase Voltage BC
V
word
40077
Phase Voltage CA
V
word
40078
Phase Voltage AN
V
word
40079
Phase Voltage BN
V
word
40080
Phase Voltage CN
V
word
40081
Scale factor [V_SF]
smallint
40083
Scale factor [W_SF]
smallint
40084
Line Frequency
Hz
word
40085
Scale factor [HZ_SF]
smallint
40086
AC Apparent Power
VA
smallint
40087
Scale factor [VA_SF]
smallint
40088
AC Reactive Power
var
smallint
40089
Scale factor [VAR_SF]
smallint
40090
AC Power Factor
Pct
smallint
40091
Scale factor [PF_SF]
smallint
40094
Scale factor [WH_SF]
smallint
40096
Scale factor [DCA_SF]
smallint
40098
Scale factor [DCV_SF]
smallint
40100
Scale factor [DCW_SF]
smallint
40101
Cabinet Temperature
C
smallint
40102
Heat Sink Temperature
C
smallint
40103
Transformer Temperature
C
smallint
40104
Other Temperature
C
smallint
40105
Scale factor [TMP_SF]
smallint
40106
Enumerated value. Operating state
word
40107
Vendor specific operating state code
word
40108
Bitmask value. Event fields
dword
40110
Reserved for future use
dword
40112
Vendor defined events
dword
40114
Vendor defined events
dword
40116
Vendor defined events
dword
40118
Vendor defined events
dword
40122
Type of DER device. Default value is 4 to indicate PV device.
word
40123
Continuous power output capability of the inverter.
W
word
40124
Scale factor
smallint
40125
Continuous Volt-Ampere capability of the inverter.
VA
word
40126
Scale factor
smallint
40127
Continuous VAR capability of the inverter in quadrant 1.
var
smallint
40128
Continuous VAR capability of the inverter in quadrant 2.
var
smallint
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB (3Q4200) - Mapping
MODBUS offset
Description
Units
Data type
40071
Phase A Current
A
word
40072
Phase B Current
A
word
40073
Phase C Current
A
word
40074
Scale factor [A_SF]
smallint
40075
Phase Voltage AB
V
word
40076
Phase Voltage BC
V
word
40077
Phase Voltage CA
V
word
40078
Phase Voltage AN
V
word
40079
Phase Voltage BN
V
word
40080
Phase Voltage CN
V
word
40081
Scale factor [V_SF]
smallint
40083
Scale factor [W_SF]
smallint
40084
Line Frequency
Hz
word
40085
Scale factor [HZ_SF]
smallint
40086
AC Apparent Power
VA
smallint
40087
Scale factor [VA_SF]
smallint
40088
AC Reactive Power
var
smallint
40089
Scale factor [VAR_SF]
smallint
40090
AC Power Factor
Pct
smallint
40091
Scale factor [PF_SF]
smallint
40094
Scale factor [WH_SF]
smallint
40096
Scale factor [DCA_SF]
smallint
40098
Scale factor [DCV_SF]
smallint
40100
Scale factor [DCW_SF]
smallint
40101
Cabinet Temperature
C
smallint
40102
Heat Sink Temperature
C
smallint
40103
Transformer Temperature
C
smallint
40104
Other Temperature
C
smallint
40105
Scale factor [TMP_SF]
smallint
40106
Enumerated value. Operating state
word
40107
Vendor specific operating state code
word
40108
Bitmask value. Event fields
dword
40110
Reserved for future use
dword
40112
Vendor defined events
dword
40114
Vendor defined events
dword
40116
Vendor defined events
dword
40118
Vendor defined events
dword
40122
Type of DER device. Default value is 4 to indicate PV device.
word
40123
Continuous power output capability of the inverter.
W
word
40124
Scale factor
smallint
40125
Continuous Volt-Ampere capability of the inverter.
VA
word
40126
Scale factor
smallint
40127
Continuous VAR capability of the inverter in quadrant 1.
var
smallint
40128
Continuous VAR capability of the inverter in quadrant 2.
var
smallint
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB A41-A42 - MODBUS Registers
MODBUS offset
Description
Units
Data type
20480
Active import, kwh
kWh
int64
20484
Active export, kwh
kWh
int64
20488
Active net, kwh
kWh
int64
20492
Reactive import, kvarh
kvarh
int64
20496
Reactive export, kvarh
kvarh
int64
20500
Reactive net, kvarh
kvarh
int64
20504
Apparent import, kvah
kVAh
int64
20508
Apparent export, kvah
kVAh
int64
20512
Apparent net, kvah
kVAh
int64
20516
Active import, kvah
kg
int64
20532
Active import, kvah
currency
int64
20848
Active import, tariff 1
kWh
int64
20852
Active import, tariff 2
kWh
int64
20856
Active import, tariff 3
kWh
int64
20860
Active import, tariff 4
kWh
int64
20880
Active export, tariff 1
kWh
int64
20884
Active export, tariff 2
kWh
int64
20888
Active export, tariff 3
kWh
int64
20892
Active export, tariff 4
kWh
int64
20912
Reactive import, tariff 1
kvarh
int64
20916
Reactive import, tariff 2
kvarh
int64
20920
Reactive import, tariff 3
kvarh
int64
20924
Reactive import, tariff 4
kvarh
int64
20944
Reactive export, tariff 1
kvarh
int64
20948
Reactive export, tariff 2
kvarh
int64
20952
Reactive export, tariff 3
kvarh
int64
20956
Reactive export, tariff 4
kvarh
int64
21600
Active import, l1
kWh
int64
21604
Active import, l2
kWh
int64
21608
Active import, l3
kWh
int64
21612
Active export, l1
kWh
int64
21616
Active export, l2
kWh
int64
21620
Active export, l3
kWh
int64
21624
Active net, l1
kWh
int64
21628
Active net, l2
kWh
int64
21632
Active net, l3
kWh
int64
21636
Reactive import, l1
kvarh
int64
21640
Reactive import, l2
kvarh
int64
21644
Reactive import, l3
kvarh
int64
21648
Reactive export, l1
kvarh
int64
21652
Reactive export, l2
kvarh
int64
21656
Reactive export, l3
kvarh
int64
21660
Reactive net, l1
kvarh
int64
21664
Reactive net, l2
kvarh
int64
21668
Reactive net, l3
kvarh
int64
21672
Apparent import, l1
kVAh
int64
21676
Apparent import, l2
kVAh
int64
21680
Apparent import, l3
kVAh
int64
21684
Apparent export, l1
kVAh
int64
21688
Apparent export, l2
kVAh
int64
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB A43-A44 - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
20480
Active import, kwh
kWh
int64
20484
Active export, kwh
kWh
int64
20488
Active net, kwh
kWh
int64
20492
Reactive import, kvarh
kvarh
int64
20496
Reactive export, kvarh
kvarh
int64
20500
Reactive net, kvarh
kvarh
int64
20504
Apparent import, kvah
kVAh
int64
20508
Apparent export, kvah
kVAh
int64
20512
Apparent net, kvah
kVAh
int64
20516
Active import, kvah
kg
int64
20532
Active import, kvah
currency
int64
20848
Active import, tariff 1
kWh
int64
20852
Active import, tariff 2
kWh
int64
20856
Active import, tariff 3
kWh
int64
20860
Active import, tariff 4
kWh
int64
20880
Active export, tariff 1
kWh
int64
20884
Active export, tariff 2
kWh
int64
20888
Active export, tariff 3
kWh
int64
20892
Active export, tariff 4
kWh
int64
20912
Reactive import, tariff 1
kvarh
int64
20916
Reactive import, tariff 2
kvarh
int64
20920
Reactive import, tariff 3
kvarh
int64
20924
Reactive import, tariff 4
kvarh
int64
20944
Reactive export, tariff 1
kvarh
int64
20948
Reactive export, tariff 2
kvarh
int64
20952
Reactive export, tariff 3
kvarh
int64
20956
Reactive export, tariff 4
kvarh
int64
21600
Active import, l1
kWh
int64
21604
Active import, l2
kWh
int64
21608
Active import, l3
kWh
int64
21612
Active export, l1
kWh
int64
21616
Active export, l2
kWh
int64
21620
Active export, l3
kWh
int64
21624
Active net, l1
kWh
int64
21628
Active net, l2
kWh
int64
21632
Active net, l3
kWh
int64
21636
Reactive import, l1
kvarh
int64
21640
Reactive import, l2
kvarh
int64
21644
Reactive import, l3
kvarh
int64
21648
Reactive export, l1
kvarh
int64
21652
Reactive export, l2
kvarh
int64
21656
Reactive export, l3
kvarh
int64
21660
Reactive net, l1
kvarh
int64
21664
Reactive net, l2
kvarh
int64
21668
Reactive net, l3
kvarh
int64
21672
Apparent import, l1
kVAh
int64
21676
Apparent import, l2
kVAh
int64
21680
Apparent import, l3
kVAh
int64
21684
Apparent export, l1
kVAh
int64
21688
Apparent export, l2
kVAh
int64
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB (B21) - MODBUS Registers
MODBUS offset
Description
Units
Data type
20480
Active import
kWh
dword
20484
Active export
kWh
dword
20488
Active net
kWh
integer
20492
Reactive import
kvarh
dword
20496
Reactive export
kvarh
dword
20500
Reactive net
kvarh
integer
20504
Apparent import
kVAh
dword
20508
Apparent export
kVAh
dword
20512
Apparent net
kVAh
integer
20516
Active import CO2
kg
dword
20532
Active import currency
currency
dword
20848
Active import tariff 1
kWh
dword
20852
Active import tariff 2
kWh
dword
20856
Active import tariff 3
kWh
dword
20860
Active import tariff 4
kWh
dword
20880
Active export tariff 1
kWh
dword
20884
Active export tariff 2
kWh
dword
20888
Active export tariff 3
kWh
dword
20892
Active export tariff 4
kWh
dword
20912
Reactive import tariff 1
kvarh
dword
20916
Reactive import tariff 2
kvarh
dword
20920
Reactive import tariff 3
kvarh
dword
20924
Reactive import tariff 4
kvarh
dword
20944
Reactive export tariff 1
kvarh
dword
20948
Reactive export tariff 2
kvarh
dword
20952
Reactive export tariff 3
kvarh
dword
20956
Reactive export tariff 4
kvarh
dword
21600
Active import L1
kWh
dword
21604
Active import L2
kWh
dword
21608
Active import L3
kWh
dword
21612
Active export L1
kWh
dword
21616
Active export L2
kWh
dword
21620
Active export L3
kWh
dword
21624
Active net L1
kWh
integer
21628
Active net L2
kWh
integer
21632
Active net L3
kWh
integer
21636
Reactive import L1
kvarh
dword
21640
Reactive import L2
kvarh
dword
21644
Reactive import L3
kvarh
dword
21648
Reactive export L1
kvarh
dword
21652
Reactive export L2
kvarh
dword
21656
Reactive export L3
kvarh
dword
21660
Reactive net L1
kvarh
integer
21664
Reactive net L2
kvarh
integer
21668
Reactive net L3
kvarh
integer
21672
Apparent import L1
kVAh
dword
21676
Apparent import L2
kVAh
dword
21680
Apparent import L3
kVAh
dword
21684
Apparent export L1
kVAh
dword
21688
Apparent export L2
kVAh
dword
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB (B23,B24) - Mapping
MODBUS offset
Description
Units
Data type
20480
Active import
kWh
int64
20484
Active export
kWh
int64
20496
Reactive export
kvarh
int64
20500
Reactive net
kvarh
int64
20504
Apparent import
kVAh
int64
20508
Apparent export
kVAh
int64
20512
Apparent net
kVAh
int64
20516
Active import CO2
kg
int64
20532
Active import currency
currency
int64
20848
Active import
kWh
int64
20852
Active import
kWh
int64
20856
Active import
kWh
int64
20860
Active import
kWh
int64
20880
Active export
kWh
int64
20884
Active export
kWh
int64
20888
Active export
kWh
int64
20892
Active export
kWh
int64
20912
Reactive import
kvarh
int64
20916
Reactive import
kvarh
int64
20920
Reactive import
kvarh
int64
20924
Reactive import
kvarh
int64
20944
Reactive export
kvarh
int64
20948
Reactive export
kvarh
int64
20952
Reactive export
kvarh
int64
20956
Reactive export
kvarh
int64
21600
Active import, L1
kWh
int64
21604
Active import, L2
kWh
int64
21608
Active import, L3
kWh
int64
21612
Active export, L1
kWh
int64
21616
Active export, L2
kWh
int64
21620
Active export, L3
kWh
int64
21624
Active net, L1
kWh
int64
21628
Active net, L2
kWh
int64
21632
Active net, L3
kWh
int64
21636
Reactiveimport, L1
kvarh
int64
21640
Reactive import, L2
kvarh
int64
21644
Reactive import, L3
kvarh
int64
21648
Reactiveexport, L1
kvarh
int64
21652
Reactiveexport, L2
kvarh
int64
21656
Reactiveexport, L3
kvarh
int64
21660
Reactivenet, L1
kvarh
int64
21664
Reactive net, L2
kvarh
int64
21668
Reactivenet, L3
kvarh
int64
21672
Apparent import, L1
kVAh
int64
21676
Apparent import, L2
kVAh
int64
21680
Apparent import, L3
kVAh
int64
21684
Apparent export, L1
kVAh
int64
21688
Apparent export, L2
kVAh
int64
21692
Apparent export, L3
kVAh
int64
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB (M2M,DMTME) - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
4096
3 phase system voltage
Volt
dword
4098
Phase voltage L1 N
Volt
dword
4100
Phase voltage L2 N
Volt
dword
4102
Phase voltage L3 N
Volt
dword
4104
Line voltage L1 2
Volt
dword
4106
Line voltage L2 3
Volt
dword
4108
Line voltage L3 1
Volt
dword
4110
3 phase system current
mA
dword
4112
Line current L1
mA
dword
4114
Line current L2
mA
dword
4116
Line current L3
mA
dword
4118
3 phase system power factor
integer
4120
Power factor L1
integer
4122
Power factor L2
integer
4124
Power factor L3
integer
4126
3 phase system cos
integer
4134
3 phase system apparent power
VA
dword
4136
Apparent power L1
VA
dword
4138
Apparent power L2
VA
dword
4140
Apparent power L3
VA
word
4142
3 phase system active power
Watt
integer
4144
Active power L1
Watt
integer
4146
Active power L2
Watt
integer
4148
Active power L3
Watt
integer
4150
3 phase system reactive power
VAr
integer
4152
Reactive power L1
VAr
integer
4154
Reactive power L2
VAr
integer
4156
Reactive power L3
VAr
integer
4158
3 phase system active energy
Wh
dword
4160
3 phase system reactive energy
VArh
dword
4192
Max line current L1
mA
dword
4194
Max line current L2
mA
dword
4196
Max line current L3
mA
dword
4198
Max 3 phase system active power
Watt
integer
4200
Max 3 phase system apparent power
VA
dword
4208
3 phase system active power 15 aver
Watt
integer
4210
3 phase system apparent power 15 aver
VA
dword
4212
Active energy L1
Wh
dword
4214
Active energy L2
Wh
dword
4216
Active energy L3
Wh
dword
4218
Reactive energy L1
VArh
dword
4220
Reactive energy L2
VArh
dword
4222
Reactive energy L3
VArh
dword
4224
Max 3 phase system active power 15 aver
Watt
integer
4226
Voltage ThdF L1
Watt
word
4228
Voltage ThdF L2
Watt
word
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB (M4M) - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
20480
Active energy - import
kWh
int64
20484
Active energy - export
kWh
int64
20488
Active energy - net
kWh
int64
20492
Reactive energy - import
kvarh
int64
20496
Reactive energy - export
kvarh
int64
20500
Reactive energy - net
kvarh
int64
20504
Apparent energy - import
kVA
int64
20508
Apparent energy - export
kVA
int64
20512
Apparent energy - net
kVA
int64
20516
Active energy - import, CO2 conversion factor
kg / kWh
int64
20532
Active energy - import, currency conversion factor
Currency / kWh
int64
20848
Active energy - import (Tariffs), 1
kWh
int64
20852
Active energy - import (Tariffs), 2
kWh
int64
20856
Active energy - import (Tariffs), 3
kWh
int64
20860
Active energy - import (Tariffs), 4
kWh
int64
20864
Active energy - import (Tariffs), 5
kWh
int64
20868
Active energy - import (Tariffs), 6
kWh
int64
20880
Active energy - export (Tariffs), 1
kWh
int64
20884
Active energy - export (Tariffs), 2
kWh
int64
20888
Active energy - export (Tariffs), 3
kWh
int64
20892
Active energy - export (Tariffs), 4
kWh
int64
20896
Active energy - export (Tariffs), 5
kWh
int64
20900
Active energy - export (Tariffs), 6
kWh
int64
20912
Reactive energy - import (Tariffs), 1
kvarh
int64
20916
Reactive energy - import (Tariffs), 2
kvarh
int64
20920
Reactive energy - import (Tariffs), 3
kvarh
int64
20924
Reactive energy - import (Tariffs), 4
kvarh
int64
20928
Reactive energy - import (Tariffs), 5
kvarh
int64
20932
Reactive energy - import (Tariffs), 6
kvarh
int64
20944
Reactive energy - export (Tariffs), 1
kvarh
int64
20948
Reactive energy - export (Tariffs), 2
kvarh
int64
20952
Reactive energy - export (Tariffs), 3
kvarh
int64
20956
Reactive energy - export (Tariffs), 4
kvarh
int64
20960
Reactive energy - export (Tariffs), 5
kvarh
int64
20964
Reactive energy - export (Tariffs), 6
kvarh
int64
21600
Active energy - import, L1
kWh
int64
21604
Active energy - import, L2
kWh
int64
21608
Active energy - import, L3
kWh
int64
21612
Active energy - export, L1
kWh
int64
21616
Active energy - export, L2
kWh
int64
21620
Active energy - export, L3
kWh
int64
21624
Active energy - net, L1
kWh
int64
21628
Active energy - net, L2
kWh
int64
21632
Active energy - net, L3
kWh
int64
21636
Reactive energy - import, L1
kvarh
int64
21640
Reactive energy - import, L2
kvarh
int64
21644
Reactive energy - import, L3
kvarh
int64
21648
Reactive energy - export, L1
kvarh
int64
21652
Reactive energy - export, L2
kvarh
int64
21656
Reactive energy - export, L3
kvarh
int64
There are more MODBUS items for this device. Please download the program to discover all registers.
ABB (Trio 50,Trio 60) - Mapping
MODBUS offset
Description
Units
Data type
1001
Inverter block modbus map size
word
1002
Inverter presence
word
1052
DC/DC converter state
word
1053
DC/AC converter state
word
1074
Partial energy
Wh
dword
1078
Monthly energy
Wh
dword
1090
Mean grid voltage (Phase to neutral)
V
single
1092
Mean output current (Phase to neutral)
A
single
1094
Output active power: instantaneous
W
single
1096
Output active power: absolute peak
W
single
1098
Output active power: daily peak
W
single
1100
Output active power: feedback on curtailment applied
W
single
1102
Reactive power: feedback on set point applied
VAr
single
1104
Power factor: feedback on set point applied
single
1106
Mean grid frequency
Hz
single
1108
Active power on DC input #1
W
single
1110
Voltage on DC input #1
V
single
1112
Current on DC input #1
A
single
1120
Internal temperature
degC
single
1122
Inverter temperature
degC
single
1126
Isolation resistance
MOhm
single
1128
Max leakage current
A
single
ABB (UNO DM PLUS) - Mapping
MODBUS offset
Description
Units
Data type
40071
Phase A Current
A
word
40072
Phase B Current
A
word
40073
Phase C Current
A
word
40074
Scale factor [A_SF]
smallint
40075
Phase Voltage AB
V
word
40076
Phase Voltage BC
V
word
40077
Phase Voltage CA
V
word
40078
Phase Voltage AN
V
word
40079
Phase Voltage BN
V
word
40080
Phase Voltage CN
V
word
40081
Scale factor [V_SF]
smallint
40083
Scale factor [W_SF]
smallint
40084
Line Frequency
Hz
word
40085
Scale factor [HZ_SF]
smallint
40086
AC Apparent Power
VA
smallint
40087
Scale factor [VA_SF]
smallint
40088
AC Reactive Power
var
smallint
40089
Scale factor [VAR_SF]
smallint
40090
AC Power Factor
Pct
smallint
40091
Scale factor [PF_SF]
smallint
40094
Scale factor [WH_SF]
smallint
40096
Scale factor [DCA_SF]
smallint
40098
Scale factor [DCV_SF]
smallint
40100
Scale factor [DCW_SF]
smallint
40101
Cabinet Temperature
C
smallint
40102
Heat Sink Temperature
C
smallint
40103
Transformer Temperature
C
smallint
40104
Other Temperature
C
smallint
40105
Scale factor [TMP_SF]
smallint
40106
Enumerated value. Operating state
word
40107
Vendor specific operating state code
word
40108
Bitmask value. Event fields
dword
40110
Reserved for future use
dword
40112
Vendor defined events
dword
40114
Vendor defined events
dword
40116
Vendor defined events
dword
40118
Vendor defined events
dword
40122
Type of DER device. Default value is 4 to indicate PV device.
word
40123
Continuous power output capability of the inverter.
W
word
40124
Scale factor
smallint
40125
Continuous Volt-Ampere capability of the inverter.
VA
word
40126
Scale factor
smallint
40127
Continuous VAR capability of the inverter in quadrant 1.
var
smallint
40128
Continuous VAR capability of the inverter in quadrant 2.
var
smallint
There are more MODBUS items for this device. Please download the program to discover all registers.